beautypg.com

Carrier 48TC**16 User Manual

Page 18

background image

18

Factory--Option Thru--Base Connections

(Electrical Connections)—
This service connection kit consists of a

1

/

2

--in electrical

bulkhead connector and a 1

1

/

2

--in electrical bulkhead

connector, connected to an “L” bracket covering the

embossed (raised) section of the unit basepan in the

condenser section. See Fig. 36. The

1

/

2

--in bulkhead

connector enables the low--voltage control wires to pass

through the basepan. The 1

1

/

2

--in electrical bulkhead

connector allows the high--voltage power wires to pass

through the basepan.

1

/

2

” ELECTRICAL

BULKHEAD
CONNECTOR

1

1

/

2

” ELECTRICAL

BULKHEAD
CONNECTOR

C10907

Fig. 36 -- Thru--the--Base Option, Shipping Position

1. Remove the “L” bracket assembly from the unit.
2. Remove connector plate assembly from the “L”

bracket and discard the “L” bracket, but retain the

washer head screws and the gasket (located between

the “L” bracket and the connector plate assembly).

NOTE: Take care not to damage the gasket, as it is
reused in the following step.

3. Place the gasket over the embossed area in the

basepan, aligning the holes in the gasket to the holes

in the basepan. See Fig. 37.

4. Install the connector plate assembly to the basepan

using 8 of the washer head screws.

NOTE: If electrical connections are not going to occur at
this time, tape or otherwise cover the fittings so that

moisture does not get into the building or conduit in the
interim.

GASKET

CONNECTOR
PLATE
ASSEMBLY

C10908

Fig. 37 -- Completing Installation of Thru--the--Base

Option

Check tightness of connector lock nuts before connecting

electrical conduits.
Field--supplied and field--installed liquid tight conduit

connectors and conduit may be attached to the connectors

on the basepan. Pull correctly rated high voltage and low

voltage through appropriate conduits. Connect the power

conduit to the internal disconnect (if unit is so equipped)

or to the external disconnect (through unit side panel). A

hole must be field cut in the main control box bottom on

the left side so the 24--v control connections can be made.

Connect the control power conduit to the unit control box

at this hole.
Units without Thru--Base Connections —

1. Install power wiring conduit through side panel open-

ings. Install conduit between disconnect and control

box.

2. Install power lines to terminal connections as shown

in Fig. 31.

Field Control Wiring —

The 48TC**16 requires an external temperature control

device. This device can be a thermostat (field--supplied)

or a PremierLink controller (available as factory--installed

option or as field--installed accessory, for use on a Carrier

Comfort Network or as a stand alone control) or the RTU

Open Controller for Building Management Systems using

non--CCN protocols (RTU Open is available as a

factory--installed option only).

Thermostat —

Install

a

Carrier--approved

accessory

2

stage

Cooling/Heating thermostat according to installation

instructions included with the accessory. If using an

electronic thermostat, configure it for “non--heat pump”

operation. Locate the thermostat accessory on a solid wall

in the conditioned space to sense average temperature in

accordance with the thermostat installation instructions.

If the thermostat contains a logic circuit requiring 24--v

power, use a thermostat cable or equivalent single leads of

different colors with minimum of seven leads. If the

thermostat does not require a 24--v source (no “C”

connection required), use a thermostat cable or equivalent

with minimum of six leads. Check the thermostat

installation instructions for additional features which

might require additional conductors in the cable.

For wire runs up to 50 ft. (15 m), use no. 18 AWG

(American Wire Gage) insulated wire (35_C minimum).

For 50 to 75 ft. (15 to 23 m), use no. 16 AWG insulated

wire (35_C minimum). For over 75 ft. (23 m), use no. 14

AWG insulated wire (35_C minimum). All wire sizes

larger than no. 18 AWG cannot be directly connected to

the thermostat and will require a junction box and splice

at the thermostat.

48TC

**16