NOTE: If gas and/or electrical connections are not going to

occur at this time, tape or otherwise cover the fittings so that
moisture does not get into the building or conduit in the
interim.

GASKET

CONNECTOR
PLATE
ASSEMBLY

C10906

Fig. 18 -- Completing Installation of Thru--the--Base

Option

The thru--base gas connector has male and female threads.

The male threads protrude above the basepan of the unit;

the female threads protrude below the basepan.
Check tightness of connector lock nuts before connecting

gas piping.
Install a

3

/

4

--in NPT street elbow (field--supplied) on the

thru--base gas fitting. Attach a

3

/

4

--in pipe nipple with

minimum length of 16--in (406 mm) (field--supplied) to

the street elbow and extend it through the access panel at

the gas support bracket. (See Fig. 19.)

3

/

4

-in NPT

STREET
ELBOW

THRU-BASE
GAS FITTING

GAS
SUPPORT
BRACKET

C10806

Fig. 19 -- Gas Line Piping

Other hardware required to complete the installation of

the gas supply line will include a manual shutoff valve, a

sediment trap (drip leg) and a ground--joint union. A

pressure regulator valve may also be required (to convert

gas pressure from pounds to inches of pressure). The

manual shutoff valve must be located within 6--ft (1.83 m)

of the unit. The union, located in the final leg entering the

unit, must be located at least 9--in (230 mm) away from

the access panel to permit the panel to be removed for

service. If a regulator valve is installed, it must be located

a minimum of 4--ft (1220 mm) away from the unit’s flue

outlet. Some municipal codes require that the manual

shutoff valve be located upstream of the sediment trap.

See Figs. 20 and 21 for typical piping arrangements for

gas piping that has been routed through the sidewall of the

curb. See Fig. 22 for typical piping arrangement when

thru--base is used. Ensure that all piping does not block

access to the unit’s main control box or limit the required

working space in front of the control box.

9” (229mm) min

Union

Shut Off

Valve

Drip
Leg

Thru-Curb Adapter

Unit Base Rail

C07469

Fig. 20 -- Gas Piping

Drip
Leg

Shut Off

Valve

Union

Thru-Curb Adapter

Burner
Access
Panel

9” (229mm) min

Unit Base Rail

C07470

Fig. 21 -- Gas Piping

C10826

Fig. 22 -- Gas Piping Thru--Base Connections