d. Refer to Table 9 for cu ft of gas per hr.
e. Multiply gas rate (cu ft/hr) X heating value (Btu/cu ft)

using natural gas heating value from local gas
utility/supplier.

EXAMPLE: (0—2000 ft altitude)
Btu heating input = Btu/cu ft X cu ft/hr
Heating value of gas = 1050 Btu/cu ft
Time for 1 revolution of 2-cu ft dial = 82 sec
Gas rate = 88 cu ft/hr (from Table 9)
Btu heating input = 88 X 1050 = 92,400 Btuh
In this example, the orifice size and manifold pressure
adjustment is within

±2 percent of the furnace input rate.

2. Set temperature rise.

Furnace must operate within range of temperature rise speci-
fied on the unit rating plate. Determine the air temperature rise
as follows.
a. Place duct thermometers in return and supply ducts as near

furnace as possible. Be sure thermometers do not "see" heat
exchangers so that radiant heat does not affect thermometer
readings. This is particularly important with straight-run
ducts.

b. When thermometer readings stabilize, subtract return-air

temperature from supply-air temperature to determine tem-
perature rise.

c. Adjust air temperature rise by adjusting blower speed.

Increase blower speed to reduce temperature rise. Decrease
blower speed to increase temperature rise.

Disconnect the electrical power before changing the speed
tap. Failure to follow this warning could result in personal
injury.

d. To change blower motor speed selections for heating mode

remove blower motor lead from control board HEAT

Table 9—Gas Rate (Cu Ft/Hr)

SECONDS

FOR 1

REVOLUTION

SIZE OF TEST DIAL

SECONDS

FOR 1

REVOLUTION

SIZE OF TEST DIAL

1

cu ft

2

cu ft

5

cu ft

1

cu ft

2

cu ft

5

cu ft

10

11

12

13

14

360

327

300

277

257

720

655

600

555

514

1800

1636

1500

1385

1286

50

51

52

53

54

72

71

69

68

67

144

141

138

136

133

360

355

346

340

333

15

16

17

18

19

240

225

212

200

189

480

450

424

400

379

1200

1125

1059

1000

947

55

56

57

58

59

65

64

63

62

61

131

129

126

124

122

327

321

316

310

305

20

21

22

23

24

180

171

164

157

150

360

343

327

313

300

900

857

818

783

750

60

62

64

66

68

60

58

56

54

53

120

116

112

109

106

300

290

281

273

265

25

26

27

28

29

144

138

133

129

124

288

277

267

257

248

720

692

667

643

621

70

72

74

76

78

51

50

48

47

46

103

100

97

95

92

257

250

243

237

231

30

31

32

33

34

120

116

113

109

106

240

232

225

218

212

600

581

563

545

529

80

82

84

86

88

45

44

43

42

41

90

88

86

84

82

225

220

214

209

205

35

36

37

38

39

103

100

97

95

92

206

200

195

189

185

514

500

486

474

462

90

92

94

96

98

40

39

38

38

37

80

78

76

75

74

200

196

192

188

184

40

41

42

43

44

90

88

86

84

82

180

176

172

167

164

450

439

429

419

409

100

102

104

106

108

36

35

35

34

33

72

71

69

68

67

180

178

173

170

167

45

46

47

48

49

80

78

76

75

73

160

157

153

150

147

400

391

383

375

367

110

112

116

120

33

32

31

30

65

64

62

60

164

161

155

150

Fig. 17—Redundant Automatic Gas Control

Valve

A00238

Fig. 18—Burner Flame

A89020

;;

;;

BURNER FLAME

BURNER

MANIFOLD

19