Table 7—Model 58ZAV Orifice Size† and Manifold Pressure for Correct Input (Continued)

(Tabulated Data Based on 23,000 BTUH Per Burner, Derated 4 percent per 1000 Ft Above Sea Level)*

ALTITUDE

RANGE

(FT)

AVG GAS

HEAT VALUE

AT ALTITUDE

(BTU/CU FT)

SPECIFIC GRAVITY OF NATURAL GAS

0.58

0.60

0.62

0.64

0.66

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

U.S.A.

Only

700

43

3.7

43

3.8

42

3.2

42

3.3

42

3.4

725

43

3.4

43

3.6

43

3.7

43

3.8

42

3.2

750

43

3.2

43

3.3

43

3.4

43

3.5

43

3.6

775

43

3.0

43

3.1

43

3.2

43

3.3

43

3.4

5001

800

43

2.8

43

2.9

43

3.0

43

3.1

43

3.2

825

43

2.7

43

2.7

43

2.8

43

2.9

43

3.0

to

850

43

2.5

43

2.6

43

2.7

43

2.8

43

2.8

875

43

2.4

43

2.4

43

2.5

43

2.6

43

2.7

6000

900

43

2.2

43

2.3

43

2.4

43

2.5

43

2.5

925

43

2.1

43

2.2

43

2.3

43

2.3

43

2.4

950

48

3.8

43

2.1

43

2.1

43

2.2

43

2.3

975

48

3.6

48

3.7

43

2.0

43

2.1

43

2.2

1000

48

3.4

48

3.5

48

3.6

48

3.7

43

2.1

ALTITUDE

RANGE

(FT)

AVG GAS

HEAT VALUE

AT ALTITUDE

(BTU/CU FT)

SPECIFIC GRAVITY OF NATURAL GAS

0.58

0.60

0.62

0.64

0.66

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

U.S.A.

Only

650

43

3.7

43

3.8

42

3.2

42

3.3

42

3.5

675

43

3.4

43

3.5

43

3.7

43

3.8

42

3.2

700

43

3.2

43

3.3

43

3.4

43

3.5

43

3.6

6001

725

43

3.0

43

3.1

43

3.2

43

3.3

43

3.4

750

43

2.8

43

2.9

43

3.0

43

3.1

43

3.2

to

775

43

2.6

43

2.7

43

2.8

43

2.9

43

3.0

800

43

2.4

43

2.5

43

2.6

43

2.7

43

2.8

7000

825

43

2.3

43

2.4

43

2.5

43

2.5

43

2.6

850

43

2.2

43

2.2

43

2.3

43

2.4

43

2.5

875

43

2.0

43

2.1

43

2.2

43

2.3

43

2.3

ALTITUDE

RANGE

(FT)

AVG GAS

HEAT VALUE

AT ALTITUDE

(BTU/CU FT)

SPECIFIC GRAVITY OF NATURAL GAS

0.58

0.60

0.62

0.64

0.66

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

U.S.A.

Only

625

43

3.4

43

3.6

43

3.7

43

3.8

42

3.2

650

43

3.2

43

3.3

43

3.4

43

3.5

43

3.6

675

43

3.0

43

3.1

43

3.2

43

3.3

43

3.4

7001

700

43

2.7

43

2.8

43

2.9

43

3.0

43

3.1

725

43

2.6

43

2.6

43

2.7

43

2.8

43

2.9

to

750

43

2.4

43

2.5

43

2.6

43

2.6

43

2.7

775

43

2.2

43

2.3

43

2.4

43

2.5

43

2.5

8000

800

43

2.1

43

2.2

43

2.2

43

2.3

43

2.4

825

48

3.7

43

2.0

43

2.1

43

2.2

43

2.2

850

48

3.5

48

3.6

48

3.7

43

2.1

43

2.1

ALTITUDE

RANGE

(FT)

AVG GAS

HEAT VALUE

AT ALTITUDE

(BTU/CU FT)

SPECIFIC GRAVITY OF NATURAL GAS

0.58

0.60

0.62

0.64

0.66

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

U.S.A.

Only

600

43

3.2

43

3.3

43

3.4

43

3.5

43

3.6

625

43

3.0

43

3.1

43

3.2

43

3.3

43

3.4

8001

650

43

2.7

43

2.8

43

2.9

43

3.0

43

3.1

675

43

2.5

43

2.6

43

2.7

43

2.8

43

2.9

to

700

43

2.4

43

2.4

43

2.5

43

2.6

43

2.7

725

43

2.2

43

2.3

43

2.3

43

2.4

43

2.5

9000

750

43

2.0

43

2.1

43

2.2

43

2.3

43

2.3

775

48

3.6

48

3.7

43

2.1

43

2.1

43

2.2

800

48

3.4

48

3.5

48

3.6

48

3.7

43

2.0

* For size 135-20 only, input is 22,500 Btuh per burner. Deduct 0.1-in. wc from manifold pressure shown in table. Change orifice size if manifold pressure falls below

3.2-in. wc on altitudes up to 2000 ft, otherwise change orifice size if manifold pressure falls below 2.0-in. wc.

† Orifice sizes shown in BOLD are factory installed.

17