Encore woodburning stove, Freestanding installations, Fireplace installations – Vermont Casting 2550 User Manual

Page 7: Above the fireplace

background image

7

Encore Woodburning Stove

2000956

ST492

Defiant

freestanding

installation

11/00

Chimney

Elbow

Slip Pipe

Standard

Connector

Oval to

Round Adapter

Flue Collar

Thimble

Flue Liner

Flue

ST492

Fig. 6 An exploded view of the chimney connection in a free-

standing masonry installation.

Securing the Single-wall Connector to a

Masonry Chimney

Both freestanding masonry chimneys and fireplace ma-

sonry chimneys may be used for your installation.

Freestanding Installations

If the chimney connector must pass through a combus-

tible wall to reach the chimney, follow the recommenda-

tions in the Wall Pass-Through section that follows.
The opening through the chimney wall to the flue

(the “breech”) must be lined with either a ceramic or

metal cylinder, called the “thimble”, which is cemented

securely in place. Most chimney breeches incorporate

thimbles, but the fit must be snug and the joint between

the thimble and the chimney wall must be cemented

firmly.
A special piece called the “thimble sleeve,” slightly

smaller in diameter than standard connectors and

most thimbles, will facilitate the removal of the chimney

connector system for inspection and cleaning. Thimble

sleeves should be available from your local dealer.
To install a thimble sleeve, slide it into the breech until

it is flush with the inner flue wall. Do not extend it into

the actual flue passage, as this could interfere with the

draft.

ST243

thinble connection

12/13/99 djt

Thimble Sleeve

Chimney Connector

Flue

Keep

sleeve

end flush

with flue

tile

ST243

Fig. 7 The thimble, made of either ceramic or metal, must be

cemented securely in place.

The thimble sleeve should protrude 1-2” (25-50mm) into

the room. (Fig. 7) Use furnace cement and thin gasket-

ing to seal the sleeve in place in the thimble. Secure

the chimney connector to the outer end of the sleeve

with sheet metal screws.
Without a thimble, a suitable length of chimney con-

nector can be extended through the breech to the inner

face of the flue liner, and cemented securely in place.

Additional pieces of connector are then attached with
sheet metal screws.

Fireplace Installations

The chimney connector may be connected to the

chimney above the fireplace opening or through the

fireplace.

Above the Fireplace

The Encore may be connected to a chimney above

a fireplace opening. (Fig. 8) In such installations, the

stove is positioned on the hearth in front of the fireplace

and the chimney connector rises from the stove top and

then angles ninety degrees back into the chimney. The

chimney liner should extend to the point at which the

chimney connector enters the chimney.
If the chimney connector from your installation enters

the chimney above a fireplace, follow all the guidelines

mentioned above for freestanding installations. In addi-

tion, give special consideration to the following points:

Check the clearance between the stove and the

chimney connector, and any combustible trim or the

mantel. Use the necessary combination of mantel, trim,

and connector heat shields to achieve the required

clearances.

Check the clearance between the chimney con-

nector and the ceiling. If no heat shields are used, the

clearance should be at least 24” (610mm). To find out

how much this clearance may be reduced with heat

shields, refer to the clearance chart on Page 14.