beautypg.com

Encore woodburning stove, Wall shields, Stove heat shields – Vermont Casting 2550 User Manual

Page 11

background image

11

Encore Woodburning Stove

2000956

In general, the greatest clearance is required when you

place a stove and its connector with no heat shields

near a wall with no heat shield.
For example, when the Encore is installed parallel to

the rear wall and no shields are used, it must be at least

31” (787mm) from the wall behind it and at least 24”

(610mm) from walls on either side.
If the Encore is installed in a corner and no shields

are used, the corners of the stove must be at least 24”

(610mm) from nearby walls.
The least clearance is required when both the stove

and its connector, as well as the wall, have heat

shields.
When shields are attached to the stove or chimney

connector, they are mounted 1” - 2” (25-50mm) away

from the stove or connector surface on noncombustible

spacers. Air flowing between the stove (and/or chimney

connector) and nearby shields carries away heat. Do

not block the air flow by filling this empty space with any

insulating material.
The shiny shield surface facing the heat source must be

left unpainted, enabling it to reflect heat back towards

the stove or connector and away from the wall.
Clearances may be reduced only by means approved

by the regulatory authority, and in accordance with the

clearances listed in this manual.
Because of their restricted air flow and heat retention

characteristics, specific construction requirements and

special clearances apply to installations into alcoves.

Refer to the diagrams on Page 10, and contact your

Vermont Castings Dealer for details before beginning
an alcove installation.
NOTE: ALCOVE INSTALLATION OF THE ENCORE
IS NOT PERMITTED IN CANADA.

Wall Shields

One way to reduce clearances is with a wall shield

constructed of 24 gauge or heavier sheet metal, or of

another noncombustible material such as 1/2” (13mm)

insulation board or common brick “laid on flat,” with the

3¹⁄₂" (90mm) side down.
Shields must be spaced out from the combustible

surface 1" (25mm) on noncombustible spacers, as in

Figure 13. The spacers should not be directly behind

the stove or chimney connector.
Air must be able to flow between the wall and the

shield. At least 50% of the bottom 1" (25mm) of the

shield should be open and the shield must be open at

the top. Use metal screening, as in Figure 14, to keep

stray objects from falling behind the shield.
The shield for a top-exit stove must extend 10"

(254mm) above the top of the stove; for a rear exit con-

figuration, the shield must be 36” (914mm) high. The

shield for the chimney connector must be 30” (762mm)

wide, centered behind the pipe; for installations that

use an approved prefabricated chimney to pass through

the ceiling, the chimney connector shield must stop 1”

(25mm) below the ceiling.

Stove Heat Shields

The Vermont Castings Encore Rear Heat Shield is one

way to reduce the clearance to the rear wall. The rear

heat shield can be installed on either rear- or top-vent-

ing stoves. However, since the chimney connector

also radiates heat toward the wall in top-venting instal-

lations, you should use a chimney connector shield

whenever you use the rear heat shield on top-venting

stoves.
Clearance reductions with the rear heat shield apply

only to the wall to the rear in parallel installations. Nei-

ther the side clearance requirement nor the clearance

requirement in corner installations may be reduced.

ST248

wall shield construction

12/14/99 djt

Air Flow

Stud Wall

Framing

Wall Shield

Noncombustible

Spacer and

Fasteners

Drywall

Airflow

Metal

Screening

Wall

Shield

Metal Lathe or

Noncombustible

Spacers

ST248

Fig. 14 Approved wall shield construction.