Concord 4 Installation Guide

9

Specifications

Pow er requirements

Class 2, 16.5 VAC, 40 VA, 60 Hz (600-1023 or
600-1024)

Rechargeable battery: 12 VDC, 4.5 or 5.0 Ah
lead-acid (60-681) or 12 VDC, 7 Ah (60-680).
The battery w ill last 24 hours w ith no AC and
specified stand-by load.

Auxiliary pow er
output

1.0 A at 9 to 14 VDC (12 VDC typical)

Radio frequency

319.5 MHz

Nominal RF range

1,000 feet (305 m) typical open air

Storage temperature

-30 to 140ºF (-34 to 60ºC)

Operating
temperature

32 to 120ºF (0 to 49ºC)

Maximum humidity

85% relative humidity, noncondensing

Dimensions (H x W x
D)

14 x 12 x 3 in. (35.6 x 30.5 x 7.6 cm)

Regulatory information

UL listed installations

This section describes the requirements for UL listed
installations.

Basic system:

Control panel (600-1021-95R Concord 4 RF, 600-1022-

95R Concord Express V4, 600-1040 Concord Commercial

V4, or 600-1042 Concord 4 Hybrid).

Standard class 2 16.5 VAC, 40 VA power transformer 22-

145 or 22-156 (600-1023), 22-156-CN, or 22-145-CN

(600-1023-CN), or power line carrier class 2 16.5 VAC, 40

VA power transformer 22-149 (600-1024) or 22-149-CN

(600-1024-CN). You must order these transformers

separately from UTC Fire & Security.

Backup battery 12 V 4.5 or 5.0 Ah (60-681) or 12 V 7 AH

(60-680).

SuperBus 2000 fixed display touchpad (60-820), FTP

1000 (600-1020), 2x16 LCD touchpad (60-746-01), ATP

1000 (60-983), ATP 2100 (60-985), ATP 2600 (60-984),

2x20 LCD touchpad (60-803), or 2x20 VFD touchpad (60-

804).

Interior speaker siren (60-528), hardwired interior siren

(13-949), or speaker siren (13-060).

Basic system but also include a SuperBus 2000 RF

receiver (60-764-95R-01) or a SuperBus transceiver (600-

1025-01-95R).

Household burglary alarm system unit (UL 1023)

Basic system plus the following:

Hardwired magnetic contact (13-068 or 13-071) or

wireless learn mode door/window sensor (60-362)

Immediate beeps set to on.

UL 98 options set to on.

Receiver failure set to on (if wireless devices are used).

Siren verify set to on.

Exit delay set to 60 seconds.

Quick exit set to off.

Siren timeout set to 4 minutes or more.

Entry delay set to 45 seconds or less.

RF TX timeout set to 24 hours (if sys tem includes built in

receiver or SuperBus 2000 RF receiver or SuperBus 2000

RF transceiver and wireless burglary sensors).

Extended delay set to off.

Sleep time set to off.

Two trip error set to off.

Alarm verify set to off.

Disable trouble beeps set to off.

Household fire warning system (UL 985)

Basic system plus the following:

Wireless smoke sensor 60-506-319.5, 60-848-02-95, or

TX-6010-01-1 learned into sensor group 26.

Immediate beeps set to on.

UL 98 options set to on.

Receiver failure set to on (if wireless devices are used).

Siren verify set to on.

Sleep time set to off.

Siren timeout set to 4 minutes or more.

Two-trip error set to off.

Disable trouble beeps set to off.

RF TX timeout set to 4 hours (if system includes built in

receiver or SuperBus 2000 RF transceiver and wireless

smoke sensors).

UL 1023 and 985 24-hour backup

For 24-hour backup, the total current draw for all

connected devices is limited to 90 mA (during normal
standby conditions) using a 4.5 or 5.0 Ah battery, or 190
mA (during normal standby conditions) using a 7.0 Ah
battery.

SIA system requirements

SIA system requirements are the same as those
described for a UL-listed basic system. If multiple
annunciation is required, use additional touchpads. This
applies to model numbers 60-746-01, 60-803, 60-804,
60-820, 60-983, 60-984, 60-985, and 600-1020. UL
requirements take priority over SIA requirements.

Table 11 on page 10 describes programming
requirements to meet ANSI-SIA CP-01.