Concord 4 Installation Guide
Table 11: SIA setting requirements
Function
Default setting
Required setting
Exit extension
On
On
Duress code
Disabled
Disabled
Dialer abort delay
30 seconds
15 to 45 seconds
Cancel message
On
On
Call w ait cancel
Disabled
On if reporting to
central station and
customer has call
w aiting service.
Entry delay
30 seconds
30 to 240 seconds
Exit delay
60 seconds
45 to 184 seconds
Sw inger limit
1
1
Smoke verify
Off
On if smoke alarms
are programmed into
system.
Cross zone
Disabled
Enabled for zones
w ith high probability of
false alarms
Table 12 below describes nonprogrammable (hard-
coded) system operation, as required to meet ANSI-SIA
CP-01 and is provided only for your reference.
Table 12: ANSI-SIA CP-01 requirements
Function
Operation
SIA false alarm
Enabled
Auto stay arming
Enabled
Disarm during entry delay
Enter code only (or 1 + CODE)
Cancel alarm
Enter code only (or 1 + CODE).
Abort annunciation
Enabled
Exit error
Enabled
Entry/exit progress annunciation
Enabled
Note:
You may use the silent arming feature to suppress
arming level and exit beeps for the current arming
period. Refer to the Concord 4 user manual for more
information on silent arming.
Commercial burglary alarm system unit (UL 1610)
Basic system using control panel 600-1040, SuperBus
2000 RF transceiver module (600-1025-01-95R), plus
the following:
•
Hardwired magnetic contact (13-068 or 13-071) or
wireless learn mode door/window sensor (60-499).
•
SAW PIR sensor (60-639-95R), crystal PIR sensor (60-
703-95R), or DS924i PIR sensor (60-511-01-95).
•
UL approved bell/housing, such as Ademco #AB12M or
equivalent.
•
Immediate beeps set to on.
•
UL 98 options set to on.
•
Receiver failure set to on (if wireless devices are used).
•
RF TX timeout set to 4 hours.
•
24-hour tamper set to on.
•
System tamper set to on.
•
Automatic phone test set to on.
•
Phone text frequency set to 1.
•
Next phone test set to 1.
•
Siren verify set to on.
•
AC failure set to on.
•
Exit delay set to 120 seconds or less.
•
Quick exit set to off.
•
Two-trip error set to off.
•
Alarm verify set to off.
•
Disable trouble beeps set to off.
•
Phone number must be programmed.
•
High level reports set to on.
•
Low level reports set to on.
•
Communication failure set to on.
•
Extended delay set to off.
•
Sleep time set to off.
•
Siren timeout set to 4 minutes or more.
UL 1610 24-hour backup
Same as UL 1023 and 985.
UL 1635 digital alarm communicator system
For UL 1635 installations, entry delay plus dialer abort
delay must not exceed 60 seconds. Same as UL 1023,
985, and 1610 plus:
•
AC failure set to on.
•
Phone number must be programmed.
•
Low CPU battery set to on.
•
Next phone test set to 1.
•
Phone test frequency set to 1.
•
High level reports set to on.
•
Low level reports set to on.
•
Communication failure set to on.
•
RF TX timeout set to 4 hours.
Central station reporting
The panel has been tested with the following central
station receivers using SIA and Contact ID reporting
formats:
•
CS-5000 central station receiver
•
Sur-Gard central station receiver with models SG-DRL2A
and SG-CPM2
•
Osborne Hoffman central station receiver