Concord 4 Installation Guide

5

Only when the display shows SYSTEM PROGRAMMING
can you advance to tier 2 programming menus.

Press B or # to advance forward through menus. Press
A or * to move backward through the menus.

Only when a specific menu is displayed can you
advance to those menu settings. For example, from the
SENSORS display, pressing # gives you access to
learning sensors, programming sensor text, deleting
sensors, and viewing/editing sensor programming.

To exit program mode:

1. Press * until the display shows SYSTEM

PROGRAMMING.

2. Press A or B until the display shows EXIT

PROGRAMMING READY.

3. Press # and the touchpad displays the time and

date.

Sensors menu

The Sensors menu gives you access to the following
settings:

Learn sensors. Add (learn) hardwired zones, wireless

sensors, and wireless touchpads into panel memory.

Sensor text. Name the sensors and zones you have

added to the system.

Delete sensors. Delete zones and sensors from panel

memory.

Edit sensors. View or change a sensor group or partition

assignment. You can also identify whether a zone is

wireless or hardwired, whether it is configured as normally

closed (NC) or normally open (NO), and whether the zone

is a touchpad.

Table 7 below describes how to trip different types of
sensors to program (learn) them in the panel.

Table 7: Tripping sensors

Sensor

How to trip the sensor

Hardw ired zones

Start w ith the zone in its normal state, and
then trip the zone into its alarm state. A
normally closed door, for example, should
be closed w hen you begin the learn
sensors process. To trip the zone, open
the door.

Wireless sensors

Follow the instructions included w ith each
sensor.

Wireless door/w indow
sensors w ith external
contacts

Place the external contact in the alarm
condition, and then activate the sensor
tamper sw itch.

Self-actuated bells

Activate the tamper sw itch.

Sensor

How to trip the sensor

Handheld w ireless
touchpads

Press the BYPASS button.

Key fobs *

Press and hold the lock and unlock
buttons together until the key fob LED
flashes.

ELM key fobs *

Press and release the unlock button tw ice
quickly, then press and hold until the LED
flashes three times.

Press and release the unlock button once
quickly, then press and hold until the LED
flashes tw o times.

Press and hold the unlock button until the
LED flashes once.


* Key fobs have not been investigated by UL for use in a UL Listed
installation.

Learn sensors

The default setting is “None”.

The panel comes with factory programmed onboard

hardwired zones. Install 2 kohm, end of line (EOL)
resistors on all unused factory sensors shown above and
hardwired zones. If you don’t want to install EOL
resistors, delete any unused zones from memory. See
Table on page 6 for onboard hardwired zone factory
programming. Sensors must be placed in a partition or
sensor group. To change the sensor group or partition
assignment after adding a sensor or zone, use the Edit
Sensors menu.

To add (learn) sensors into panel memory:

1. With the display showing SENSORS, press #.

The display shows LEARN SENSORS.

2. Press #.

The display shows SENSOR PTN 1.

3. Press # to select partition 1 or press 2, 3, 4, 5, or 6

and then press # to select the desired partition.

The display shows SENSOR GROUP 0.

4. Enter the sensor group and press #. (See Table for

a description of all sensor group characteristics.)

The display shows TRIP SENSOR nn, where nn is
the displayed (next available) sensor number.

5. To change the displayed sensor number, enter the

desired sensor number and press #.

The desired sensor number is displayed.

6. With the desired sensor number displayed, use the

guidelines in Table 6 to force the sensor or zone you