Start-Up and Maintenance Documentation
START-UP AND MEASUREMENTS SHOULD BE PERFORMED AFTER THE SYSTEM HAS BEEN
AIR BALANCED AND WITH THE COOLING ON (Warranty will be void without completion of this
form).
Job Information
Job Name
Service Company
Address
Address
City
City
State
State
Zip
Zip
Phone Number
Phone Number
Fax Number
Fax Number
Contact
Contact
Purchase Date
Start-Up Date
Unit Information
Refer to the start-up procedure in this manual to complete this section.
Name Plate and Unit Information
Field Measured Information
Model Number
Motor Voltage
MUA Serial Number
Motor Amperage**
Motor Volts
MUA Blower RPM
Motor Hertz
Ambient Wet Bulb Temp
°F
Motor Phase
Ambient Dry Bulb Temp
°F
Motor FLA
COND 1 Suction Pressure
PSI
Motor HP
COND 1 Suction Temperature
°F
Blower Pulley
COND 1 Liquid Pressure
PSI
Motor Pulley
COND 1 Liquid Temperature
°F
Belt Number
COND 1 Subcooling
°F
Gas Type
COND 1 Superheat
°F
Min. Btu/Hr
COND 2 Suction Pressure
PSI
Max. Btu/Hr
COND 2 Suction Temperature
°F
COND 1 Serial Number
COND 2 Liquid Pressure
PSI
COND 2 Serial Number
COND 2 Liquid Temperature
°F
COND 3 Serial Number
COND 2 Subcooling
°F
COND 2 Superheat
°F
COND 3 Suction Pressure
PSI
COND 3 Suction Temperature
°F
COND 3 Liquid Pressure
PSI
COND 3 Liquid Temperature
°F
COND 3 Subcooling
°F
COND 3 Superheat
°F
Cooling Thermostat Set-Point
°F
Airflow Direction
Correct
Incorrect
**
If measured amps exceed the FLA rating on the nameplate, fan RPM must be reduced to decrease the
measured amps below the nameplate FLA rating.