beautypg.com

Caution, Warning – Carrier 58HDX User Manual

Page 17

background image

17

1. Connect Y-terminal in furnace as shown for proper blower operation.
2. Some thermostats require a “C” terminal connection as shown.
3. If any of the original wire, as supplied, must be replaced, use same

type or equivalent wire.

FIELD 24--V WIRING

FIELD 115--, 208/230--, 460--VWIRING

FACTORY 24--VWIRING

FACTORY 115--V WIRING

NOTE 2

208/230-- OR

460--V

THREE

PHASE

208/230--V

SINGLE

PHASE

FURNACE

115--V FIELD--

AUXILIARY

O

SUPPLIED

J--BOX

L

DISCONNECT

24--V

TERMINAL

TWO

BLOCK

THREE--WIRE

HEATING--ONLY

FIVE WIRE

DISCONNECT

NOTE 1

FIELD--SUPPLIED

CONDENSING

UNIT

WIRE

C

O

N

T

R

R

G

WC

RG

Y

GND

GND

BLOWER DOOR SWITCH

WHT

BLK

WHT

BLK

W

GND

THERMOSTAT

TERMINALS

A02174

NOTES:

Fig. 17 -- Field Wiring

A07727

Blower Off
Delay Jumper

24 VAC
HUM

FUSE

115 VAC
HUM

Diagnostic Light

EAC

Fig. 18 -- Control Center

4. Check igniter resistance. Igniter resistance is affected by

temperature. Only check resistance when the igniter is at
room temperature.

a. Using an ohm meter, check resistance across both

igniter leads in connector.

b. Cold reading should be between 40 ohms and 70 ohms.

5. Remove igniter.

BURN HAZARD
Failure to follow this caution may result in personal injury.
Allow igniter to cool before removal. Normal operating

temperatures exceed 2000°F (1093°C).

CAUTION

!

a. Using a 1/4 in. nut driver, remove the single screw

securing the igniter bracket to the burner box and

carefully withdraw the igniter through the bottom of the
burner box without striking the igniter on surrounding
parts.

b. Inspect igniter for signs of damage or failure.

UNIT DAMAGE HAZARD
Failure to follow this caution may result in premature failure

of the igniter.

The igniter is fragile. DO NOT allow it to hit the side of the

burner box opening while removing or replacing it.

CAUTION

!

c. If replacement is required, replace igniter on igniter

bracket and then install assembly into burner box to
avoid damage to the igniter.

6. To replace igniter and bracket assembly, reverse items 5a

and 5b.

7. Reconnect igniter wire connection.

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury

or death.
Igniter wires must be securely placed in slot in manifold

grommet or else they could become pinched or severed and

electrically shorted.

!

WARNING

58H