Installation instructions (cont’d), Venting through roof - clearances – Kenmore THE ECONOMIZER 153.33298 User Manual

Page 11

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

Installation Instructions (cont’d)

POWER VENT TERMINAL

24"

7= NATURAL DRAFT (GRAVITY),

i..... X

/ DIRECT VENT, POWER VENT

---------- H ( ')) / OR POWER DIRECT VENT

'

— APPLIANCE INLET AND/OR

'

OUTLET VENT(S)

Venting Through Roof - Clearances

• 0" clearance for 3'’ (or optional 2") PVC, ABS, or CPVC Schedule

40 piping from combustible surfaces.

• The location selection must provide clearances for servicing and

proper operation of the water heater. Figure 4.

• The Power Vent outlet terminal shall terminate at least 18” above the

roof surface. Figure 5.

The venting system must be installed in a manner which allows

inspection of the installation of the venting pipes and joints as
well as periodic inspection after installation as required by ANSI
Standards.

Figure 5

Figure 3 c

MUST MAINTAIN

ADEQUATE SERVICE
AND MAINTENANCE
ACCESSIBILITY, ^

Figure 4

range

of

degrees

AVAILABLE FOR VENT

PIPE INSTALLATION,

11