4. BUFFER TANK FIELD PIPING

An AERCO boiler system should be piped in one of four arrangements, depending on your

system design requirements and the boiler specified. Benchmark boilers can be installed with a

2-port buffer tank. Modulex boilers should be installed with a 4-port buffer tank.

For illustration

purposes, AERCO SmartPlate water heaters are depicted in the piping diagrams presented in

these instructions.
Select the appropriate piping diagrams for your application from the following drawings:

NOTE

Each AERCO boiler requires a minimum flow when used in DHW

combination systems – see figures below for specific minimum

flow requirements for each boiler model.

Figure 2 shows the buffer tank and SmartPlate heaters piped as a zone with the Benchmark

boilers and the heating system.

Figure 3 shows the buffer tank and SmartPlate heaters, piped as a zone with the

Benchmark boilers and the heating system, and a separate zone, or summer pump. In this

arrangement the system pump supplies the buffer tank/SmartPlate zone during the heating

season. When the heating season ends, the system pump can be shut down and the zone

will be serviced by the separate summer pump to conserve energy.

Figure 4 shows the buffer tank and SmartPlate heaters piped with Benchmark boilers

dedicated solely to domestic water heating.

Figure 5 shows the 4-port buffer tank and SmartPlate heaters piped with Modulex boilers.

The location of connections on the 4-port buffer tank, and natural stratification will ensure

that the hot outlet water for the boilers will pass through to the system and the colder return

water will pass through back to the boilers and allow condensing.

A non-AERCO low mass boiler system should be piped as shown in Figure 6. In this

illustration, SmartPlate water heaters and a 4-port buffer tank are piped as a zone of the

heating system.

IMPORTANT!

The piping schematics shown in these installation procedures

illustrate only the piping between the water heater and the

AERCO tank. SEE THE APPROPRIATE WATER HEATER

OPERATIONS AND MAINTENANCE MANUAL FOR COMPLETE

WATER HEATER INSTALLATION INSTRUCTIONS.