V. electrical installation – Kistler-Morse KM InvisiLink User Manual
Page 10

www.kistlermorse.com
6
97-1502-13 Rev. C
V.
ELECTRICAL INSTALLATION
WARNING: REMOVE POWER FROM THE UNIT BEFORE INSTALLING, REMOVING OR MAKING
ADJUSTMENTS
GENERAL SAFETY
When using electrical equipment, you should always follow basic safety precautions, including the
following:
• The installation/wiring of this product must comply with all national, federal, state, municipal,
and local codes that apply.
• Properly ground the enclosure to an adequate earth ground.
• Do not modify any factory wiring. Connections should only be made to the terminals
described in this section.
• All connections to the unit must use conductors with an insulation rating of 300 V minimum,
rated for 105 C, a minimum flammability rating of VW-1, and be of appropriate gauge for the
voltage and current required (see specs).
• Do not allow moisture to enter the electronics enclosure. Conduit should slope downward
from the housing. Install drip loops and seal conduit with silicone rubber product.
DISCONNECT REQUIREMENTS FOR PERMANENTLY INSTALLED EQUIPMENT
A dedicated disconnecting device (circuit breaker) must be provided for the proper installation
of the unit. If independent circuits are used for power input, individual disconnects are required.
Disconnects must meet the following requirements:
• Located in close proximity to the device
• Easily accessible to the operator
• Appropriately marked as the disconnect for the device and associated circuit
• Sized appropriately to the requirements of the protected circuit (See Specifications)
RS-485/RS-422 EQUIPMENT MATRIX
COMMUNICATION
DEVICE
RS-485
RS-422
Bindicator 3D Level Scanner
x
Bindicator Mark-4/GP-4 Yo-Yo
x
Bindicator/Kistler-Morse ORB
x
x
Bindicator/Kistler-Morse ORB 4-20mA Input Box
x
Bindicator SonoTracker
x
Kislter-Morse Ultrawave
x
Kistler-Morse MVS
x
Kistler-Morse STXplus
x
Kistler-Morse SVS2000
x
Kistler-Morse Weigh II
x
Niagara Meters 5600 Controller
x
Note: RS-485 Communication will be programmed at a baud rate of 115200;
RS-422 Commuication will be programmed at a baud rate of 9600.