Network Configuration 33
•
•
•
•
•
•
•
Status Error code 3 (out of tolerance)
•
2: TARE CMD. Write a #2 to the command register to ZERO the net weight. The status
register will read 0 if this command succeeds:
•
Status Error code 1 (motion)
•
Status Error code 2 (A/D error)
•
4: WRITE NONVOL CMD. Write a #4 to the command register to save parameters in
non-volatile memory.
•
No Error Codes
•
0x64 (100 decimal): CAL LOW CMD. Write a 0x64 hex to the command register to
perform the low step of a traditional calibration. The status register will read 0 if this
command succeeds:
•
Calibration_Fail 1
•
Calibration_Fail_Motion 3
•
Calibration_Fail_Adc_Error 4
•
0x65 (101decimal): CAL HIGH CMD. Write a 0x65 hex to the command register to
perform the high step of a traditional calibration.
•
Calibration_Fail 1
•
Calibration_Fail_Motion 3
•
Calibration_Fail_Adc_Error 4
•
HardcalFailCounts 8: not enough counts between hard cal hi and hard cal lo
•
0x66 (102 decimal): C2 CAL CMD. Write a 0x66 hex to the command register to
perform a C2 calibration.
•
Calibration_Fail 1
•
Calibration_Fail_Motion 3
•
Calibration_Fail_Adc_Error 4
•
Calibration_Fail_Noc2 5
•
Calibration_Fail_C2capeq 6
•
Calibration_Fail_C2clones 7
•
0x1000 (4096 decimal): WRITE INTEGER CMD. Set the value of an integer
parameter. Write 0x1000 in the command register 0, the parameter ID number in
registers 2, 3 and the desired value in registers 4, 5.
•
No Error Codes
•
0x1001 (4097 decimal): WRITE FLOAT CMD. Set the value of a floating point
parameter. Write 0x1001 in the command register 0, the parameter ID number in
registers 2, 3 and the desired float value in registers 4, 5.
•
Failure 1