Line voltage connections 5-pole – Steffes Transceiver User Manual
Page 14

11
Line Voltage Connections 5-POLE
WARNING:
Hazardous Voltage. Can cause injury or death.
Route line-voltage conductors (circuit board power and controlled-load circuits)
and make line-voltage connections only in the line-voltage connection area.
Use only copper conductors that are rated for 75° C minimum.
Route low-voltage conductors (remote outdoor sensor, power company signal/control switch,
override switch, etc.) only into the low-voltage connection area.
Install in accordance with applicable local, state, and national codes and regulations.
SecureGround™ Ground Bond
NOTE: This transceiver has SecureGround™ ground wire bond points. Use this procedure to
connect line-voltage ground wires to the enclosure throughout this installation instruction.
1.
If used, connect ground wire to SecureGround™ screw by removing 1±1/8" (25.4±3 mm) insulation from
ground wire.
NOTE: Anchor hole accepts 14 to 10 AWG solid conductor.
2.
Insert end of wire into SecureGround™ anchor hole. Hold wire firmly and bend it clockwise, 350º around
screw shank.
IMPORTANT: Make sure no insulation is between wire and screw head.
3.
Tighten screw securely.
1.
The transceiver can be powered with 120 VAC or
208/240 VAC. Before connecting power to the
transceiver, the circuit board MUST be tapped for
the appropriate input voltage as shown.
NOTE: 208VAC/240VAC is factory default.
2.
Route line voltage wiring to the transceiver and
connect to L1 and L2 terminals on Circuit #1 as
shown to the right.
120VAC
240
VAC
L1 L2