Line Voltage Connections 5-POLE

WARNING:

Hazardous Voltage. Can cause injury or death.

Route line-voltage conductors (circuit board power and controlled-load circuits)
and make line-voltage connections only in the line-voltage connection area.

Use only copper conductors that are rated for 75° C minimum.

Route low-voltage conductors (remote outdoor sensor, power company signal/control switch,
override switch, etc.) only into the low-voltage connection area.

Install in accordance with applicable local, state, and national codes and regulations.

SecureGround™ Ground Bond

NOTE: This transceiver has SecureGround™ ground wire bond points. Use this procedure to

connect line-voltage ground wires to the enclosure throughout this installation instruction.

1.

If used, connect ground wire to SecureGround™ screw by removing 1±1/8" (25.4±3 mm) insulation from
ground wire.

NOTE: Anchor hole accepts 14 to 10 AWG solid conductor.

2.

Insert end of wire into SecureGround™ anchor hole. Hold wire firmly and bend it clockwise, 350º around
screw shank.

IMPORTANT: Make sure no insulation is between wire and screw head.

3.

Tighten screw securely.

1.

The transceiver can be powered with 120 VAC or
208/240 VAC. Before connecting power to the
transceiver, the circuit board MUST be tapped for
the appropriate input voltage as shown.

NOTE: 208VAC/240VAC is factory default.

2.

Route line voltage wiring to the transceiver and
connect to L1 and L2 terminals on Circuit #1 as
shown to the right.

120VAC

240

VAC

L1 L2