U TTW SERVICE PROCEDURE XI

115 VAC Trace

WARNING

115 volt potential exposure. Use caution

making voltage checks to avoid personal injury.

Disconnect cord set as

shown in photo 27.

LED status

None, Control LED not

on or flashing.

Step 1.

Verify 115VAC and proper polarity at wall outlet.

Step 2.

With unit plugged in and control power switch in the “ON” position verify LED status.

LED status

Short flash, once every

four seconds.

LED status

“Heartbeat”, alternates

bright/dim.

LED status

Various flashing error

codes.

Waiting for

call for heat.

Thermostat calling

for heat

Verify error code as

listed on page 12

Using a volt meter set to

volts AC, is there 115VAC

across terminals shown

in photo 28?

N

Y

27

28

Reconnect cord set
shown in photo 27.

Repair damage

Check for damage to AC

supply power cord.

Y

N

Replace Blower

31

Check for 115VAC between black & white wires.

-NOTE-

Electronic meter probes required. Use care not to

damage connector during this check.

Wire sheath pulled back to

identify wire colors

30

Wire harness

Disconnect wire harness

from gas control

(see photo 30).

Locate black & white wires at connector, It

may be necessary to pull back wire sheath

to identify wire colors

(see photo 31).

Y

N

Replace gas

control.

Is there 115VAC across

black & white wires as

shown in photo 31?

Call for technical

support.

Is there 115VAC across

terminals shown in

photo 29?

N

Y

Incorrect supply

voltage polarity

29

Page 32

115 VAC Circuit Trace

R

32