beautypg.com

Bradford White U-TW4-75S-76R-3N User Manual

Page 17

background image

U TTW SERVICE PROCEDURE II

Burner Operation Inspection,

Cleaning and Replacement

Page 17

At periodic intervals (not more than 6 months) a visual inspection should be made of the main burner for proper operation
and to insure no debris is accumulating.

Main burner should light smoothly from pilot and burn with a blue flame with a minimum of yellow tips. After
approximately 5 minutes of operation the burner screen will become radiant and the flame will soften and turn orange. If
the burner screen does not become radiant after 5 minutes of operation it must be cleaned (see burner cleaning procedure
below).

Main burner must be free from any debris accumulation that may affect burner operation (see burner cleaning procedure
below).

DANGER

Under no circumstances shall flammable materials be used or stored in the vicinity of the water heater. If
flammable vapors are present, a fire or explosion may result causing property damage, personal injury or
death.

WARNING

Inner door and burner components may be HOT when performing this operation. Take

necessary precaution to prevent personal injury.

¼” Hex Drive Manifold

Cover Screws

¼” Hex Drive Manifold

Bracket Screws

Manifold Cover

Main Burner Inspection, Cleaning and Replacement

Burner Cleaning

Step 1.

Remove burner and inner door assembly per SERVICE PROCEDURE I, steps 3 through 4.

Step 2.

Remove manifold cover from burner inner door by removing (2) ¼” hex drive screws and then sliding
manifold cover to the right. Use a stiff brush, compressed air and/or shop vacuum to remove any debris
build up from the manifold mount.

Step 3.

Remove manifold brackets from burner by removing (4) ¼” hex drive screws.