U TTW SERVICE PROCEDURE V

Blower Testing and Replacement

WARNING

115 volt potential exposure. Use caution when

making voltage checks to avoid personal injury.

Blower Testing

Is there 115VAC across

terminals shown in

photo 15?

Incorrect supply

voltage polarity

Determine

power source

problem and

correct.

Does blower energize Within 2

minutes?

Y

Disconnect cord set

shown in photo 12. Is

there 115VAC across

terminals shown in photo

14?

N

See pressure switch

testing

Page 20.

Is there 115 VAC at

wall outlet?

Check power cord

for damage.

Y

N

Disconnect

pressure switch

tubing from blower

(see photo 11).

Connect

manometer to

pressure tap of

blower

(see photo 11).

With blower running, and exhaust

adapter removed from top of blower,

is there a negative pressure of -2.15"

to -2.30" W.C.?

Step 1.

Position gas control power switch
to “ON” position and adjust control to call for heat.

Step 2.

Remove the three screws (Phillips Screw driver)
from control access cover on blower assembly and
remove cover (see photos 9 and 10).

Reconnect cord set shown

in photo 12, is there

115VAC between blue wire

and green ground wire

(see photo 16).

Replace blower

Does cord set

have electrical

continuity?

Disconnect vent

system from top of

blower and remove

vent adapter

(see photo 13).

Does blower energize after 2

minutes, run for 30 seconds

and shut down?

N

Is there 115vac across blue

and green wires

(see photo 16)?

Blower OK

Y

Repair or replace

power cord

Replace blower

Y

N

N

N

N

Y

Y

Y

Y

N

Pressure switch

tubing

Pressure tap

Remove exhaust

adapter

Shown with pressure

switch removed.

Green ground

wire

Blue wire

Replace blower

Y

Determine voltage

problem and correct.

N

Page 22

10

11

12

14

15

16

13

Replace gas

control

Y

Replace

cord set

N

Control

Access

Cover

Screws

9

R

22