beautypg.com

Troubleshooting guide – Vintage Cellars SC Series WhisperKOOL User Manual

Page 24

background image

SC

033114

Page 22 | 1-800-343-9463

TROUBLESHOOTING GUIDE

Unit has ice forming on the evaporator

Possible Cause

Evaporator coil is dirty

Something is blocking the supply and/or return air

Evaporator fan is not turning on

Unit has not gone through its Anti-Frost sequence


Unit continues to ice

Unit does not run/power up

Possible Cause

Unit is not plugged in

Power switch not on

Line voltage is incorrect rating for unit

Bottle at set point

Thermostat not calling for cooling

Power select switch in wrong position

Faulty thermostat or wiring

Cellar Temperature is to Warm

Possible Cause

Temperature of the room unit is exhausting to has

exceeded 85°F

Unit is undersized for the cellar

Something is blocking the supply and/or return air,

on evaporator or condenser side of the unit

Unit is mounted too low in the cellar

One or more of the fans is not turning on

Compressor is not turning on

Compressor keeps cycling on overload

Poor seal around door

Controller set too high

Evaporator coil is frosted or iced up

Solution

Clean coil with a vacuum
If coil is very dirty, use a spray bottle with a small amount of liquid
dish washing detergent. Spray coil, let set for 5 min, then flush
with fresh water

Remove blockage
Call a service tech to troubleshoot
Check for ice in the depth of the coil. Melt with blow drier until
coil is warm to the touch. Soak up water with a towel
Observe ice formation pattern. If only part way up the coil face,
unit could be low on refrigerant. If all the way up, the coil may be
dirty or airflow is blocked

Solution

Make sure the unit is plugged into an outlet
Turn unit on by pressing the power button on the control
Check line voltage to make sure there is 110 V/120 V
Lower set point
Lower set point
See page 10 for correct switch position
Call Customer Service at 1-800-343-9463

Solution

Intake temperature needs to drop below 85°F

Order correct size unit
Remove air flow obstruction

Re-locate unit so the distance from the ceiling and top of the
unit is no more than 18”

Call Customer Service at 1-800-343-9463
Call Customer Service at 1-800-343-9463
Make sure all fans are working and there is no airflow obstruction
Make sure there are no air gaps around the door. If door seal is
damaged, replace it
Lower the set point
Observe ice formation pattern. If only part way up the coil face,
unit could be low on refrigerant. If so, call Customer Service at
1-800-343-9463