Smart Power Systems Liberator Series User Manual
Page 33

Smart Power
®
Systems
A. C. MODULAR GENERATOR SYSTEM
Page 32 of 54
power output (electrical PLUS hydraulic) of the system in kilowatts (reference 
Figure 21). 
The system controller is 
configured to operate a generator 
whose maximum output is this 
number (in kW). 
The
LI indicates the system
controller is configured to 
operate an LI-series 
Generator 
Example of configuration display
Figure 21
d. If there are no active faults, pressing the Mode switch once more will return the
Command & Control Center to its normal mode. If there are active faults, they 
will be displayed in succession, one each time you press the Mode switch. 
See Diagnostics in the trouble shooting section for more information on faults.
 
8. 
Alarms, Shutdowns and Overrides provided by the Command and Control Center
The following is a list of diagnostic faults displayed by the Command and Control 
Center that will cause an automatic shutdown of the system (see the Diagnostic 
Faults section of this manual for a complete list of diagnostic faults.): 
a.
OIL HOT. If the system measures a hydraulic oil temperature that exceeds 
175°F (79°C), the system will begin displaying an alarm. If the system 
measures a hydraulic oil temperature that exceeds 180°F (82°C), the generator 
will automatically shut down in 30 minutes unless the shutdown is overridden. If 
the temperature of the hydraulic oil reaches 220°F (104°C), the system will 
immediately shut down (above 220°F (104°C) the shutdown cannot be 
overridden). 
b.
OIL LO. If the system detects an insufficient level of hydraulic fluid in the 
reservoir, it will begin displaying an alarm. The generator will automatically be 
shut down in 30 minutes unless the shutdown is overridden, or the fault is 
cleared by adding sufficient fluid. 
c.
Unb LOAD. If the system measures an electrical load imbalance between Line1 
and Line 2 of more than 20% of the system’s total wattage rating, the generator 
will automatically shut down in 30 minutes unless the shutdown is overridden. 
See Step 7, of the “Installation Guide” for more information on balancing loads 
applied to the generator. 