Smart Power Systems Liberator Series User Manual
Page 28
Smart Power
®
Systems
A. C. MODULAR GENERATOR SYSTEM
Page 27 of 54
displays the string “
0FF” as shown in Figure 14, press the On/Off switch to turn
the generator off, if needed.
g. Check for hydraulic fluid leaks, all hose connections must be tight. Monitor the
hydraulic fluid level in both the A.C. modular generator system and the
XRT system, adding fluid to both as needed.
WARNING: The A.C. modular generator system and the XRT rescue tool pump
use DIFFERENT hydraulic fluids. ONLY the A.C. generator system
uses Dexron III hydraulic fluid. Reference the XRT manual for hydraulic fluid
information for the XRT rescue tool pump .
h. After 10 minutes, the system controller will automatically switch the generator to
“
0N”. Check to see that the generator is turning (The frequency display should
indicate
0n). If it is not, press the On/Off switch on the Command & Control
Center to start the generator.
i. After the generator has been operated for 20 minutes with the generator on, the
system controller will automatically disable the purge option.
Verify that the generator’s output frequency is 59-63 Hz. If the frequency is not
within that range, contact Smart Power Systems at (231) 832-5525 for more
information.
11.
Prior to applying full load, and after the oil temperature is above 100°F verify proper
operation of the cooler fan by feeling for airflow being pushed out of the tray
assembly. If the air is not being pushed through the cooler face contact Smart
Power
®
Systems at (231) 832-5525 for more information. Also verify that the air
passing through the cooler and the fan is not restricted.
WARNING:
The SPS Model LI-15, LI-20, and LI-25 have been pre-set at the factory to provide
correct frequency and voltage. No pump adjustment is required. If it appears the
pump needs to be adjusted, contact Smart Power
®
Systems at (231) 832-5525 before
proceeding. Damage to generator from improper pump adjustment will void the
system’s warranty.
Improper ventilation will result in system overheating, reduced performance and
possible damage to the system and/or cause personal injury. If the system is
installed such that improper ventilation exists, the system’s warranty will be voided.