Rice Lake 920i Programmable HMI Indicator/Controller - Analog Output Card User Manual
Page 4

Important
Connection to PLC Analog Input Module
If the PLC analog input uses a common ground (negative input of the analog card) and both PLC
channels are connected to the same option card, there is crosstalk and the values of the 2 inputs will be
merged.
Example: If one is inputting 6 mA and the other is inputting 12 mA they will merge and each looks like it is
inputting 9 mA.
6 + 12 / 2 = 9 mA
To prevent this cross talk, the PLC must have isolated grounds on the input channels.
Specifications
Resolution
16-bit, monotonicity over temperature
Linearity
±0.03% of full scale input
Current Output
0–20 mA or 4–20 mA (20% offset)
Maximum Load Resistance
840
Power consumption
3.9W (max. load @ 20 mA)
Voltage Output
0–10 VDC
Minimum Load Resistance
1.1 K
Power consumption
3.9W (max. load @ 10 VDC)
Input Protection
Short circuit protection, 300W transient voltage suppression
Protection for ESD, EFT (electrical fast transients), tertiary lightning, and system-generated
transients per IEC 60001-4-2, 60001-4-4, and 60001-4-5; European Standards EN50082
and EN61000-4