beautypg.com

FEBCO LF886V Lead Free MasterSeries Reduced Pressure Zone Detector Prevention Assembly (Type-II) User Manual

Relief valve size: 2, Installation instructions, Warning

background image

LF860, LF866, LF880V, LF886V

Relief Valve

Size: 2

1

2

" - 10"

IS-F-860-DIAPH

INSTALLATION INSTRUCTIONS

WARNING

!

Read this Manual BEFORE using this equipment.
Failure to read and follow all safety and use information can

result in death, serious personal injury, property damage, or

damage to the equipment.
Keep this Manual for future reference.

O-Ring

Upper guide

Inner diaphragm

retainer

4x Inner diaphragm

retainer screw

Round edge of bead

to seat in groove of

upper guide

Inner diaphragm plate

Torque hand-tight to

11-16 in-lbf (1.2 - 1.8 N-m)

DO NOT OVER-TIGHTEN

Inner diaphragm

Fabric side to be on

outside of part at installation

NOTICE

Proper installation of FEBCO Relief Valve Inner Diaphragm into the Relief Valve

Upper Guide for Models LF860, LF866, LF880V, LF886V

Failure to install inner diaphragm in this method will result in the inner diaphragm burst-

ing after installation.