beautypg.com

Installation considerations – Carrier TP-NHP User Manual

Page 5

background image

3

INSTALLATION CONSIDERATIONS

Power

This control is powered by 24VAC only. It requires 24VAC (Rh and/or Rc and C

terminals) of the low−voltage transformer to be connected to it for proper

operation. It will not operate without these 2 connections. Rh and Rc are

connected via PCB breakout jumper. See Fig. 1. For applications using two

24VAC transformers, one in the indoor unit and one in the outdoor unit, connect

the common from each to the C terminal. Connect R from the indoor unit to the

Rh terminal. Connect R from the outdoor unit to the Rc terminal. Then, break

jumper on the circuit board. The W signal is taken from the Rh power and the G

signal is taken from the Rc power. If the thermostat has been installed in a

two−transformer application that is later changed to a single−transformer

installation, installer must install a field supplied jumper between Rc and Rh.

Depending on the installation, up to 14 wires may be required. Installation as

two−piece unit is recommended. Only 2 wires are required for connection

between Display Module and Equipment Control Module. These two wires (V+

and Vg) do not provide ordinary 24VAC. They carry a combination of power

and communications data that is unique to these products.

This manual is related to the following products: