Carrier TP-NHP User Manual
Page 49
47
Table 3 – Equipment Configuration Outputs
For COOL, HEAT and Emergency Heat modes, the following chart shows the
state for each output in each stage of operation
EQUIP
CONFIG
OPTION 01
HARD-
WARE
CONFIG
COOL
STG 1
COOL
STG 2
HEAT
STG 1
HEAT
STG 2
HEAT
STG 3
HEAT
STG 4
EM
HEAT
STG 1
EM
HEAT
STG 2
SS AC
AC
Y/Y2
-
W/W1
-
-
-
-
-
SS AC
HP
2S
Y/Y2
-
W/W1
W/W1
O/W2/B
(if
Opt32
+2)
-
-
-
-
SS HP
RVS
+ O
HP
Y/Y2,
O/W2/B
-
Y/Y2
Y/Y2,
W/W1
-
-
W/W1
-
SS HP
RVS
+ B
HP
Y/Y2
-
Y/Y2,
O/W2/B
Y/Y2,
W/W1,
O/W2/B
-
-
W/W1
-
SS HP
RVS
+ O
Opt43 = On
2S
Y/Y2,
O/W2/B
-
Y/Y2
Y/Y2,
W/W1
Y/Y2
Y1/W2
Y/Y2
W/W1
Y1/W2
W/W1
W/W1
Y1/W2
SS HP
RVS
+ B
Opt43 = On
2S
Y/Y2
-
Y/Y2,
O/W2/B
Y/Y2,
W/W1,
O/W2/B
Y/Y2,
Y1/W2,
O/W2/B
Y/Y2,
Y1/W2,
W/W1
O/W2/B
W/W1
W/W1
Y1/W2
2SPD AC
2S
Y1/W2
Y/Y2,
Y1W2
W/W1
W/W1
O/W2/B
-
-
-
-
2SPD HP
RVS
+ O
2S
Y1/W2
O/W2/B
Y1/W2
Y/Y2
O/W2/B
Y1/W2
Y1/W2
Y/Y2
Y1/W2
Y/Y2
W/W1
-
W/W1
-