Three−Minute Minimum on Time
In normal operation, when a stage turns on, it will not turn off for a minimum of

3 minutes. If the setpoint is changed, this timer is canceled, allowing the

equipment to turn off immediately when the demand is removed.
Heat/Cool Setpoints (Desired Temperature)
A minimum difference of 1

_ and maximum of 6_ is enforced between heating

and cooling desired temperatures. This is done by allowing 1 setting to “push”

the other, to maintain this difference. This difference is adjustable via

Configuration Option 11.

Equipment On Indicators

When cooling equipment is on, a COOL ON icon is displayed. While cooling

equipment operation is delayed by the timeguard or cycle timer, COOL ON will

flash. The same is true for HEAT ON.
When the W is energized in a heat pump, the auxiliary heat on icon will be

displayed.
Auto Changeover
When auto changeover mode is selected, a change from heat to cool (or vice

versa) will not occur until an opposite mode demand has existed for 20 minutes.

If setpoint is changed, 20−minute requirement is deleted.
Emergency Heat Mode
When AC/HP Control is configured as a heat pump and emergency heat is

selected, all Y signals are locked out, and W becomes energized upon a call for

heat.