Network Upgrades for NMC and MCU Firmware
17
Determine the upgrade completion status (see Table 2).
Table 2. Upgrade Completion Status
Message Display
Description
Successful
If the firmware upgrade is successful, a successful notification message displays. This
procedure is completed.
Not Successful
If errors occur during the upgrade, an error notification message displays.
To retry the upgrade, perform the following:
1. Beginning with step 4, click Discover again and retry the upgrade procedure.
2. If retrying the upgrade fails, contact Dell User Support at
www.support.dell.com
.
Upgrade Denied
The Upgrade Denied error message displays because network upgrades are disabled
in the Dell
t Device Power Interconnect (DPI) Web interface (see Figure 16).
To enable network upgrades and retry the upgrade, perform the following:
1. Access the DPI Web interface.
2. From the DPI Control Menu, select Network, then select Control.
3. On the Network Control page, reset the Network Upgrade attribute to Enabled
(see Figure 17).
NOTE: See the Web Interface Operation chapter of the
Dell Metered Rack Power
Distribution Unit (rPDU) User's Guide for more information.
4. Beginning with Step 4, click Discover again and retry the upgrade procedure.
5. If retrying the upgrade fails, contact Dell User Support at www.support.dell.com.
Figure 16. Identifying the Network Upgrade Disabled Setting