Carrier PC 111 User Manual

Page 58

background image

58

LEGEND AND NOTES FOR FIG. 57

NOTES:
1.Connect TRAN1 to

for 460 v units. Connect to

for 230 v

units. If 208/230 v units are run with a 208 v power supply con-
nect to

.

2.Connect TRAN2 to BLK lead for 460 v units. Connect to ORN

lead for 230 v units. If 208/230 v units are run with a 208 v
power supply connect to RED lead.

3.Circuit breaker must trip amps are equal to or less than 156%

FLA (full load amps) for CB1 and CB2. All others are 140%.

4.If any of the original wire furnished must be replaced, it must

be replaced with type 90° C wire or its equivalent.

5.Number(s) indicates the line location of contacts. A bracket

over (2) numbers signifies single pole double throw contacts.
An underlined number signifies a normally closed contact.
Plain numbers (no lines), signify a normally opened contact.

6.Condenser fan motors are thermally protected.
7.Three phase motors are protected under primary single phas-

ing conditions.

ALM

Alarm

IGVM — Inlet Guide Vanes Motor

C

Contactor

LAT

Leaving-Air Temperature

CB

Circuit Breaker

LPS

Low-Pressure Switch

CCB

Control Circuit Breaker

MTR

Motor

COMP — Compressor

MV

Main Valve

CH

Crankcase Heater

NC

Normally Closed

CR

Control Relay

NO

Normally Open

DPS

Differential Pressure Switch

OFC

Outdoor Fan Contactor

DPT

Discharge Pressure Transducer

OFM

Outdoor (Condenser) Fan Motor

EAT

Enering-Air Temperature

OMR

Outdoor Motor Relay

EC

Enthalpy Control

PCB

Power Exhaust Circuit Breaker

ECR

Economizer Close Relay

PEC

Power Exhaust Contactor

EOR

Economizer Open Relay

PEDM — Power Exhaust Damper Motor

EQUIP — Equipment

PEM

Power Exhaust Motor

FS

Fan Status Switch

P, PL

Plug

GND

Ground

RCB

Return Fan Circuit Breaker

HIR

Heat Interlock Relay

RES

Resistor

HPS

High-Pressure Switch

RFC

Return Fan Contactror

HR

Heater Relay

RFM

Return Fan Motor

HTR

Heater

SCT

Saturated Condensing Thermistor

IDC

Induced Draft Contactor

TB

Terminal Block

IDM

Induced Draft Motor

TRAN — Transformer

IFC

Indoor (Evaporator) Fan Contactor

U

Unloader

IFCB

Indoor Fan Circuit Breaker

VFD

Variable Frequence Drive

IFM

Indoor Fan Motor

Field Wiring

IGV

Inlet Guide Vanes

Factory Wiring

H4

H3

H2