Configuration header, Dip switches, 26 table 9 — potentiometer inputs and ranges – Carrier PC 111 User Manual

Page 26: Table 11 — configuration header jumpers

background image

26

Table 9 — Potentiometer Inputs and Ranges

*Optional factory-installed economizer is required. Potentiometer P2 is not a set point.

†Accessory two-step demand limit module is required (which has 2 potentiometers), or a 5 to 20 k-ohm

field-supplied potentiometer is required for single-step demand limit.

**Accessory temperature reset is required.

NOTE: Potentiometers P1-P6 input data to pin terminal connector J3.
Potentiometer P7 inputs data to pin terminal connector J1.

Configuration Header —

The configuration header is a

series of 8 small wires that are broken (open circuit) or unbro-
ken (closed circuit) in a pattern to indicate several unique char-
acteristics of the unit. The configuration header is factory set
and should not be changed; changing the factory setting may
cause the unit to malfunction.

Before start-up, visually check the configuration header

against the factory setting for the unit size. See Table 10 for
factory settings. See Table 11 for purpose for each jumper.

Table 10 — Configuration Header and

DIP Switch Factory Settings

LEGEND

*Depending on factory-installed options or field-installed accessories.

Table 11 — Configuration Header Jumpers

LEGEND

DIP Switches —

The DIP switches configure the unit for

several factory-installed options and field-installed accessories,
plus factory unloaders. The DIP switches are located under a
plastic enclosure which must be removed for access. See
Fig. 1. The switches can be field adjusted. Switches must only
be adjusted when control power is deenergized. See Table 12
for DIP switch purposes and Table 10 for factory settings of the
switch positions.

POTENTIOMETER

DESCRIPTION

LOCATION

CONTROL

VALID

RANGE

DEFAULT VALUE

P1

Supply Air

Set Point

Display

Board

45 to 70 F

45 F if -22 F < P1 < 45 F
70 F if P1 > 70 F OR IF P1 < -22 F

P2*

Economizer

Position

Economizer

Motor

0 to 100%

None (0 if P2 is bad)

P3

Reset Limit

Accessory

Board

0 to 80 F

None (limited to 70 F maximum)

P4†

Demand Limit,

Single-Step

Main Control Box

0 to 100%

None

DLCM-P1

Demand Limit,

2-Step

DLCM Board

50 to 100%

None

DLCM-P2

DLCM Board

0 to 49%

None

P5*

Minimum Economizer

Position

Accessory Board

0 to 100%

None

P6

Warm-Up

Set Point

Accessory Board

40 to 80 F

40 F if 0° F < P6 < 40 F OR IF P6 < 95 F
OR IF P6 < 0
80 F if 80 F < P6 < 95 F

P7**

Reset

Temperature

Reset Board

40 to 100 F

None

JUMPER OR
SWITCH NO.

UNIT SIZES

034-038,

048-088

UNIT SIZE

044

UNIT SIZE

104

Header

Position

Switch

Position

Header

Position

Switch

Position

Header

Position

Switch

Position

1

Off

Off

Off

2

Off

Off

Off

3

On/Off*

On/Off*

On/Off*

4

On/Off*

On/Off*

On/Off*

5

Off

Off

Off

6

Off

On

On

7

On

Off

Off

8

Off

Off

Off

DIP

Dual, In-Line Package

Broken Jumper (open circuit)

Unbroken Jumper (closed circuit)

JUMPER

NUMBER

FUNCTION

FACTORY

SETTING

MEANING

1,2

Unit Type

VAV Rooftop Unit

3,4,5

Qty Compressors

2 Compressors

6

Expansion Valve

TXV

7

Power Frequency

60 Hz

8

Not Used

No Significance

TXV — Thermostatic Expansion Valve
VAV — Variable-Air Volume

Broken Jumper (open circuit)

Unbroken Jumper (closed circuit)

Disconnect control power before changing the settings of
the DIP switches. To disconnect control power, open the
control circuit breaker.