Carrier PC 111 User Manual

Page 17

background image

17

EXAMPLE:

T10 desired set point is 70 F.
T10

R

from Table 4 for 70 F is 5929 ohms.

P7

R

= 13,084 – 5929

P7

R

= 7155 ohms

Using an ohmmeter, set the P7 potentiometer to 7155 ohms

to achieve a reset initiation set point of 70 F.
Potentiometer P3 — Reset limit set point (maximum tempera-
ture value for modified supply air set point). Maximum of 70 F,
minimum 40 F. Set between leaving air set point (P1) and 70 F
(maximum range permitted by control).

OPERATING SEQUENCE — If space temperature is above
reset set point (T10 > P7), no reset will occur.

If space temperature is equal to or less that reset set point

(T10 < P7), the LED will display 20 and reset will begin.

Control will automatically adjust leaving air temperature by

the following formula:
MSP = SP + [(P3 - SP) / 3] x (P7 – T10)
where:
MSP = Modified Leaving-Air Set Point
SP

= Supply-Air Set Point

P3

= Maximum Supply-Air Temperature (reset limit)

P7

= Reset Initiation Temperature (reset set point)

T10 = Actual Space Temperature
3

= Ratio for reset (F) (fixed parameter)

Table 4 — Thermistor Resistance and Voltage

Drop Characteristics

TEMP

(F)

RESISTANCE

(Ohms)

VOLTAGE

DROP (v)

31.0

16813.8

3.582

32.0

16345.7

3.553

33.0

15892.2

3.523

34.0

15452.7

3.494

35.0

15026.7

3.464

36.0

14613.9

3.434

37.0

14213.6

3.404

38.0

13825.5

3.373

39.0

13449.2

3.343

40.0

13084.2

3.312

41.0

12730.1

3.281

42.0

12386.6

3.250

43.0

12053.3

3.219

44.0

11730.0

3.187

45.0

11416.1

3.156

46.0

11111.5

3.124

47.0

10815.8

3.093

48.0

10528.7

3.061

49.0

10250.0

3.029

50.0

9979.3

2.997

51.0

9716.5

2.965

52.0

9461.3

2.933

53.0

9213.4

2.901

54.0

8972.6

2.869

55.0

8738.6

2.837

56.0

8511.4

2.805

57.0

8290.6

2.772

58.0

8076.1

2.740

59.0

7867.7

2.708

60.0

7665.1

2.676

61.0

7468.3

2.644

62.0

7277.1

2.612

63.0

7091.2

2.581

64.0

6910.6

2.549

65.0

6735.1

2.517

66.0

6564.4

2.486

67.0

6398.6

2.454

68.0

6237.5

2.423

69.0

6080.8

2.391

70.0

5928.6

2.360

71.0

5780.6

2.329

72.0

5636.8

2.299

73.0

5497.0

2.268

74.0

5361.2

2.237

75.0

5229.1

2.207

76.0

5100.8

2.177

77.0

4976.0

2.147

78.0

4854.8

2.117

79.0

4736.9

2.088

80.0

4622.4

2.058

034-048: TB3
054-104: TB4

034-048: TB3
054-104: TB4

OCCUPIED/UNOCCUPIED

SWITCH

NIGHT SETBACK THERMOSTAT

1

2

4

6

5

7

N.C.

N.O.

V

FIELD
SUPPLIED
POWER
SOURCE

SIGNAL
TO ROOM
TERMINALS

034-048: TB3
054-104: TB4

3

4

NOTES:

1. Occ/Unocc switch closes when occupied.
2. Night setback thermostat closes when in night setback heating.

Fig. 23 — Occupied/Unoccupied Switch with

Night Setback Thermostat

Fig. 24 — Heat Interlock Relay

Fig. 25 — Accessory Reset Board

034-048: TB3