Table 7 — Switch Functions

*Not required on 48FM and 50FM,FS units (units with high capacity power exhaust).

LEGEND

Air Pressure Tubing —

Before options such as inlet

guide vanes (IGV), variable frequency drive (VFD), and/or
modulating power exhaust can operate properly, the pneumatic
tubing for pressure sensing must be installed. Use fire-retardant
plenum tubing (field-supplied). Tubing size depends on type of
control device (see Table 8 below). Tubing must be run from
the appropriate sensing location (in the duct or in the building
space) to the control device location in the unit.

Table 8 — Tubing Size

INLET GUIDE VANES — The tubing for the duct pressure
(DP) control option should sample supply duct pressure about

2

/

3

of the way out from the unit in the main trunk duct, at a

location where a constant duct pressure is desired.

The inlet guide vanes are controlled by a differential pres-

sure switch (DPS). On sizes 034-048, the DPS is located in the
auxiliary control box at the economizer end of the unit (see
Fig. 33). On sizes 054-104, the DPS is located in the supply fan
section. See Fig. 34. Use a nominal

3

/

8

-in. plastic tubing.

SUPPLY FAN VARIABLE FREQUENCY DRIVE — The
tubing for the duct pressure (DP) control option should sample
supply duct pressure about

2

/

3

of the way out from the unit in

the main trunk duct, at a location where a constant duct pres-
sure is desired.

The duct pressure is sensed by a pressure transducer. The

pressure transducer output is directed to the VFD. On 034-048
units the DP transducer is located in the auxiliary control box.
On 054-104 units, the DP transducer is located in the supply
fan section. See Fig. 34. Use a nominal

1

/

4

-in. plastic tubing.

SWITCH

NUMBER

CONFIGURATION

VOLTAGE

FUNCTION

SW-1

N.C.

115

Deenergize 115-v (OFC, Comp, IFC, Electric Heaters)

SW-2

N.C.

115

Deenergize TRAN7 (Process Board)

SW-3

N.O.

24

Energize EOR (Open Economizer Outside Air Dampers)

SW-4

N.O.

115

Energize IFC and CR-3 (IGV/VFD)

SW-5

N.C.

115

Isolate IFC and PEC for Separate Operation

SW-6

N.O.

115

Energize PEC (Power Exhaust)

SW-7

N.O.

24

Open PED at DPS (48FK,JK and 50FK,JK Units) Force Power Exhaust VFD
to Maximum Speed (48FM and 50FM,FS Units)

SW-8*

N.C.

24

Block Auto-Close at DPS (Due to Low BP)

SW-9A/B

A: N.O.
B: N.C.

115 max

Signal Room Terminals to Open (HIR1)

BP

Building Pressure

DPS — Differential Pressure Switch
EOR — Economizer Open Relay
HIR — Heat Interlock Relay
IFC — Indoor Fan Contactor
IGV — Inlet Guide Vane
N.C. — Normally Closed
N.O. — Normally Open
PEC — Power Exhaust Contactor
PED — Power Exhaust Damper
OFC — Outdoor Fan Contactor
VFD — Variable Frequency Drive

OPTION

UNITS

NOMINAL TUBE

SIZE (in.)

Inlet Guide Vanes (IGV)

ALL

3

/

8

Supply Fan Variable

Frequency Drive (VFD)

ALL

1

/

4

Modulating Power Exhaust

FK,FKX,JK,JKX

3

/

8

FM,FS

1

/

4