Step 2 — rig and mount the unit, Step 3 — complete refrigerant piping connections – Carrier 38AKS013-024 User Manual
Page 8

Step 2 — Rig and Mount the Unit
Be sure unit panels are securely in place prior to
rigging.
RIGGING — These units are designed for overhead rigging
only. For this purpose, the transverse base channels extend
beyond the sides of the unit, with holes provided in the end
plates to attach cables or hooks. Rig with top skid packaging
assembly in place to prevent unit damage by the rigging cable.
As further protection for the coil faces, plywood sheets can
be placed against the sides of the unit, behind the cables.
Run the cables to a central suspension point so that the angle
from the horizontal is not less than 45 degrees. Raise and set
the unit down carefully.
If it is necessary to roll the unit into position, mount
the unit on longitudinal rails, using a minimum of 3 rollers.
Apply force to the rails, not the unit. If the unit is to be skid-
ded into position, place it on a large pad and drag it by the
pad. Do not apply any force to the unit.
Raise from above to lift unit from the rails or pad when
unit is in final position.
COMPRESSOR MOUNTING — As shipped, the compres-
sor is held tightly in place by self-locking bolts. Before start-
ing unit, loosen self-locking bolts until the snubber washer
can be moved sideways with finger pressure. Do not
remove shipping bolts. See Fig. 3.
Step
3
—
Complete
Refrigerant
Piping
Connections
IMPORTANT: A refrigerant receiver is not provided with
the unit. Do not install a receiver.
SIZE REFRIGERANT LINES — Consider the length of pip-
ing required between outdoor unit and indoor unit (evapo-
rator), the amount of liquid lift, and compressor oil return.
See Tables 3-5B and also refer to Part 3 of Carrier System
Design Manual and E20-II
software for design details and
line sizing. Refer to indoor unit installation instructions for
additional information.
NOTE: Use the piping data in Tables 3-5B as a general guide
only. For more precise calculations, refer to Carrier System
Design manual or E20-II software.
Condensing units with multiple-step unloading may
require double suction risers to assure proper oil return at
minimum load operating condition. See Tables 4A-5B and
Fig. 4. Reduction of evaporator coil surface should be ana-
lyzed to provide sufficient refrigerant velocity to return oil
to the compressor. Liquid line solenoid valves may be used
in certain situations to accomplish this. Hot gas bypass, if
used, should be introduced before the evaporator.
Note that refrigerant suction piping should be insulated.
Table 3 — Liquid Line Data
UNIT
38AKS
MAXIMUM
ALLOWABLE
LIQUID LIFT
ft (m)
LIQUID LINE
60 Hz
50 Hz
Maximum
Allowable
Pressure
Drop
psig (kPa)
Maximum
Allowable
Temp.
Loss
F (C)
Filter Drier
and
Sight Glass
Flare Conn.*
in. (mm)
013
52 (15.8)
7 (48.3)
2 (1.1)
5
⁄
8
(15.88)
014
67 (20.4)
016
82 (25.0
024
87 (26.5) 86 (26)
*Inlet and outlet.
NOTE: Data shown is for units operating at 45 F (7.2 C) saturated
suction and 95 F (35 C) entering air.
Table 2 — Weight Distribution
UNIT
38AKS
WEIGHT
Total
Operating
Support Point
A
B
C
D
E
F
lb
kg
lb
kg
lb
kg
lb
kg
lb
kg
lb
kg
lb
kg
013
732
332
94
43
93
42
93
42
149
68
151
68
152
69
013C
825
374
119
54
116
53
115
52
157
71
159
72
159
72
014
779
353
95
43
94
43
94
43
164
74
166
75
166
75
014C
919
417
131
59
129
59
128
58
176
80
177
80
178
81
016
789
358
95
43
95
43
96
44
167
76
168
76
168
76
016C
929
421
131
59
130
59
130
59
178
81
180
82
180
82
024
900
408
119
54
114
52
113
51
179
81
185
84
190
86
024C
1040
472
155
70
150
68
146
66
191
87
196
89
202
92
Fig. 3 — Compressor Mounting
8