beautypg.com

Troubleshooting guide – Ames Fire & Waterworks 4000CIV Cast Iron Reduced Pressure Zone Assemblies User Manual

Page 7

background image

7

Troubleshooting Guide

Problem

Cause

Solution

A. Valve spits periodically

from the vent

A.1 Fluctuating supply pressure.

A.1 Install a soft seated check valve immediately upstream

of the de vice.

A.2 Fluctuating downstream pressure

A.2 Install a soft seated check valve downstream of the

device close as possible to the shutoff valve.

B. Valve drips continually

from the vent

B.1 Fouled first check

B.1 Flush valve. If flushing does not resolve problem, dis-

assemble valve and clean or re place the first check.

B.2 Damage or fouled relief valve seat.

B.2 Clean or replace the relief valve seat.

B.3 Relief valve piston O-ring not free to

move due to pipe scale, dirt or build

up of mineral deposits.

B.3 Clean, grease or replace the piston O-ring.

B.4 Excessive back pressure, freezing, or

water hammer has distorted the sec-

ond check.

B.4 Elim i nate source of excessive backpressure or water

hammer in the system downstream of the device. Use

Watts No. 15 to eliminate water hammer. Replace

defective second check assembly.

In case of freezing; thaw, dis as sem ble and inspect

internal components.

Replace as necessary.

B.5 Electrolysis or relief valve seat or first

check seats.

B.5 Replace relief valve seat or inlet cover.

Electrically ground the piping system and/or electri-

cally isolate the device with plastic pipe immediately

upstream and down stream of the device.

B.6 Valve improperly reassembled.

B.6 If valve is dis as sem bled during installation, caution

must be exercised to install check springs in their

proper location.

C. Valve exhibits high

pressure drop.

C.1 Fouled strainer.

C.1 Clean strainer element or replace.

C.2 Valve too small for flows encountered. C.2 Install proper size device based upon

flow requirements.

D. No water flows down-

stream of valve.

D. Valve installed backwards.

D. Install valve in accordance with flow direction arrow.

E. Valve does not test

properly

E.1 Follow manufacturer’s test procedure

E.1 Clean or replace gate valve with full port ball valves or

resilient wedge shutoff valves.

E.2 Leaky downstream gate valve.

E.2 Clean or replace gate valve with full port ball valves or

resilient wedge shutoff valves.

F. Valve quickly and

repeatedly fouls follow-

ing servicing.

F. Debris in pipe line is too fine to be

trapped by strainer.

F. Install finer mesh strainer element in the strainer.

G. Winterization of back-

flow preventers.

G. Electric heat-tape wrap closely together around valve

body. Build a small shelter around the valve

with a large light bulb installed and left on at all times.

If supply line is not used during the winter, removal

of the com plete body is the best. This would create

an air gap to eliminate any possible backflow.