950 series, Rate-of-flow valve with pressure reducing feature, Model – Ames Fire & Waterworks 951GS Stainless Steel Rate-of-Flow Control Valve with Pressure Reducing Feature User Manual
Page 2
![background image](/manuals/607081/2/background.png)
01/06
950 Series
Model
8550 Hansen Road
•
Houston, Texas 77075
•
(Ph) 713.943.0688
•
(Fx) 713.944.9445
•
www.amesfirewater.com
RATE-OF-FLOW VALVE with
PRESSURE REDUCING FEATURE
951
651
Installation Guidelines
• Prior to installation, flush line to remove debris.
• Install valve horizontally “in line” (cover facing UP), so flow arrow matches flow through the line. Avoid
installing valves 6” or large vertically. Consult factory prior to ordering if installation is other than
described.
• Install inlet and outlet isolation valves. NOTE: When using butterfly valves, insure disc does not contact
control valve. Damage or improper valve seating may occur.
• Provide adequate clearance for valve servicing and maintenance.
• Install pressure gauges to monitor valve inlet and outlet pressure.
• Install Orifice Plate Assembly (provided) 3 to 5 pipe diameters downstream of the 950 / 650 with the
sensing connections offset from top of pipeline to avoid air accumulation. The Orifice Plate Assembly
should not be installed next to a butterfly valve.
• Connect Orifice Plate Assembly to Rate-of-Flow Pilot using 3/8” diameter minimum copper tubing (field
installed) in accordance with factory piping schematic.
Other AMES Rate-of-Flow Control Valves
950 / 650
Rate-of-Flow Control Valve
950-01 / 650-01
Rate-of-Flow Control Valve with Hydraulic Check Feature
950-15 / 650-15
Rate-of-Flow Control Valve with Solenoid (On-Off) Feature
952 / 652
Rate-of-Flow Control Valve with Pressure Sustaining Feature