Table 10 — Fan Performance 48TF004 — Vertical Discharge Units, High-Static Motor
LEGEND
*Motor drive range is 1075 to 1455 rpm. All other rpms require a field-
supplied drive.
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Values include losses for filters, unit casing, and wet coils. See
Table 7 for accessory/FIOP static pressure information.
3. Maximum continuous bhp is 2.4 and the maximum continuous
watts are 2120. Extensive motor and electrical testing on these
units ensures that the full range of the motor can be utilized with
confidence. Using your fan motors up to the wattage ratings shown
will not result in nuisance tripping or premature motor failure. Unit
warranty will not be affected. See Table 6 — Motor Data for addi-
tional information.
4. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative for details.
5. Interpolation is permissible. Do not extrapolate.
Table 11 — Fan Performance 48TF005 — Vertical Discharge Units, Standard Motor
LEGEND
NOTES:
1. Values include losses for filters, unit casing, and wet coils. See
Table 7 for accessory/FIOP static pressure information.
2. Extensive motor and electrical testing on these units ensures that
the full range of the motor can be utilized with confidence. Using
your fan motors up to the wattage ratings shown will not result in
nuisance tripping or premature motor failure. Unit warranty will not
be affected. See Table 6 — Motor Data for additional information.
3. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative for details.
48TF004 (3 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*
Airflow
(Cfm)
External Static Pressure (in. wg)
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
900
673
0.18
179
805
0.25
249
911
0.34
338
988
0.43
428
1061
0.47
487
1000
709
0.22
219
835
0.30
298
937
0.38
378
1039
0.49
487
1086
0.55
547
1100
746
0.26
259
867
0.35
348
964
0.40
398
1068
0.55
547
1109
0.61
607
1200
785
0.32
318
903
0.41
408
994
0.50
497
1090
0.64
637
1156
0.68
676
1300
826
0.38
378
942
0.48
477
1047
0.60
597
1122
0.70
696
1190
0.76
756
1400
868
0.45
448
984
0.57
567
1067
0.67
666
1160
0.84
766
1237
0.85
845
1500
911
0.53
527
1029
0.66
656
1109
0.77
766
1190
1.00
855
1271
0.95
945
48TF004 (3 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* (cont)
Airflow
(Cfm)
External Static Pressure (in. wg)
1.2
1.4
1.6
1.8
2.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
900
1105
0.57
567
1140
0.63
622
1170
0.68
674
1198
0.73
723
1224
0.77
771
1000
1136
0.63
627
1172
0.69
688
1203
0.75
745
1232
0.80
799
1258
0.86
852
1100
1145
0.67
666
1181
0.73
731
1213
0.80
792
1242
0.85
850
1268
0.91
906
1200
1210
0.74
736
1248
0.81
808
1282
0.88
875
1312
0.94
939
1340
1.01
1000
1300
1266
0.84
836
1306
0.92
917
1341
1.00
993
1373
1.07
1066
1402
1.14
1136
1400
1349
0.93
925
1391
1.02
1015
1492
1.11
1100
1463
1.19
1180
1494
1.26
1257
1500
1383
1.05
1044
1426
1.15
1146
1465
1.25
1242
1500
1.34
1332
1532
1.43
1419
Bhp
— Brake Horsepower Input to Fan
FIOP
— Factory-Installed Option
Watts — Input Watts to Motor
48TF005 (4 TONS) — STANDARD MOTOR (DIRECT DRIVE)
Airflow
(Cfm)
Low Speed
High Speed
208 V
230, 460, 575 V
208 V
230, 460, 575 V
Esp
Bhp
Watts
Esp
Bhp
Watts
Esp
Bhp
Watts
Esp
Bhp
Watts
1200
0.68
0.41
458
0.74
0.45
506
0.74
0.51
572
0.85
0.56
632
1300
0.61
0.42
471
0.67
0.46
521
0.66
0.52
589
0.78
0.58
651
1400
0.53
0.45
503
0.59
0.49
556
0.59
0.54
616
0.70
0.60
681
1500
0.45
0.47
536
0.51
0.52
593
0.52
0.56
631
0.63
0.62
698
1600
0.36
0.49
557
0.42
0.54
616
0.45
0.58
654
0.56
0.64
723
1700
0.26
0.52
584
0.32
0.57
646
0.37
0.60
678
0.48
0.66
750
1800
0.15
0.54
610
0.22
0.60
674
0.30
0.62
698
0.41
0.68
772
1900
0.04
0.56
629
0.11
0.62
696
0.23
0.64
720
0.34
0.70
796
2000
—
—
—
—
—
—
0.16
0.66
744
0.26
0.73
823
Bhp
— Brake Horsepower Input to Fan
Esp
— External Static Pressure (in. wg)
FIOP — Factory-Installed Option