Litz contact only by means of connector sleeves with insulating

enclosures for reasons of shock protection according to EN 61010.

Do not otherwise assign contacts that have been left unassigned ex

factory. We recommend to screen all sensor terminal leads and to

ground the shield on one side. Shields on both sides are recommen-

ded in case of RF interference or in case of equipotential bonding

over long distances. The sensor leads should not be in the same

phase winding as the mains supply and the output contact leads.

3.2 Inputs and outputs

Sensing range

Resolution

Input resistance

±10 V

1 mV

1 MΩ

±60 V

10 mV

1 MΩ

±100 mV

0,1 mV

100 MΩ

±20 mA

1 μA

12 Ω

Relay outputs (SET 1, SET 2)

Switching voltage max

250 VAC / 110 VDC

Switching current max.

1 A

Switching performance max.

150 VA / 30 W

3.3 Voltage supply connection
There are several options for operation supply. Power supply must

be fed in via the recommended external fuse.

Operating voltage

External protection

85...265 VAC, (50/60 Hz) and 100...300 VDC

M 200 mA

21...53 VAC, (50/60 Hz) and 10.5...70 VDC

M 1 A