beautypg.com

Carrier MODULINE 37HS User Manual

Page 36

background image

Table 10 — Minimum Static Pressure at Control

(Master) Unit — Units with System-Powered

Controls and Standard Diffusers

AIRFLOW

(Cfm)

37HS1

37HS2

37HS4

PLENUM SIZE (in.)

7 x 7

7 x 7

9 x 9

5 x 7

9 x 9

9 x 9

11 x 11

11 x 11

11 x 11

13 x 13

Minimum Static Pressure (in. wg)

40

0.75

0.75

N/A

N/A

50
60
70

80

0.75

0.75

0.75

N/A

90

100

110

0.90

0.90

0.75

N/A

120

N/A

N/A

0.75

N/A

140

160

N/A

N/A

0.75

0.75

180
200

220

N/A

N/A

0.90

0.75

240

N/A

N/A

N/A

0.75

280
320
360
400

440

N/A

N/A

N/A

0.90

N/A — Not Applicable
NOTE: Maximum inlet pressure — 3.0 in. wg.

Table 11 — Additional

P for

Extended Lengths of Flexible Duct

FLEX

DUCT

DIAM

(in.)

TOTAL

CFM

IN AIR

SERIES

ADDITIONAL

P PER

10 FT FLEX DUCT

(in. wg)

6

400

0.2

8

800

0.16

10

1100

0.1

12

1600

0.07

Table 12 — Additional

P for

Flexible Duct with 90-Degree Bend

FLEX

DUCT

DIAM

(in.)

TOTAL

CFM

IN AIR

SERIES

RADIUS

OF

BEND

(in.)

ADDITIONAL

P

FOR 90° BEND

IN FLEXIBLE DUCT

(in. wg)

6

400

18

0.26

8

800

24

0.16

10

1100

30

0.08

12

1600

36

0.04

C — Controller

Fig. 23 — Three 37HS2 Moduline

Units in Adjoining Modules

Fig. 24 — Four 37HS2 Moduline Units in Alternate Series Modules

36