beautypg.com

Application data (cont) – Carrier EVERGREEN 23XRV User Manual

Page 18

background image

18

Application data (cont)

ELASTOMERIC PAD

23XRV ISOLATION WITH ACCESSORY SOLEPLATE PACKAGE

TYPICAL ISOLATION

STANDARD ISOLATION

ACCESSORY SOLEPLATE DETAIL

VIEW X-X

NOTES:

1. Dimensions in ( ) are in millimeters.
2. Accessory soleplate package includes 4 soleplates, 16 jacking screws and leveling

pads. Requires isolation package.

3. Jacking screws to be removed after grout has set.
4. Thickness of grout will vary, depending on the amount necessary to level chiller. Use

only pre-mixed non-shrinking grout, Ceilcote 748 or Chemrex Embeco 636 Plus
Grout, 0

-1

1

/

2

 (38.1) to 0-2

1

/

4

 (57) thick.

5. Service clearance under the chiller is enhanced if leveling pads are not extended

along the entire length of the heat exchangers.

VIEW Y-Y

ISOLATION WITH ISOLATION PACKAGE ONLY

(STANDARD)

NOTE: Isolation package includes 4 elastomeric pads.

a23-1647