Electrical data – Carrier EVERGREEN 23XRV User Manual
Page 10
![background image](/manuals/60324/10/background.png)
10
VFD FRAME SIZES
*Maximum limits only. Additional application limits apply that will reduce these ampacities.
AUXILIARY RATINGS*
*Factory wired to VFD.
†Minimum circuit ampacity of 15 amps.
FRAME SIZE
MAX INPUT CURRENT*
MAX OUTPUT CURRENT*
AA
440
442
BA
520
442
BB
520
520
CC
608
608
ITEM
VOLTAGE
MAXIMUM
PROTECTIVE DEVICE
SIZE (AMPS)
WATTS
Controls, Oil Pump And Heater Circuit†
115
15
—
Oil Pump
115
1.48
130
Oil Sump Heater
115
4.35
500
Oil Vaporizer Heater Circuit†
115
15
—
Oil Vaporizer Heater
115
13
1500
Electrical data