beautypg.com

Electrical data – Carrier EVERGREEN 23XRV User Manual

Page 10

background image

10

VFD FRAME SIZES

*Maximum limits only. Additional application limits apply that will reduce these ampacities.

AUXILIARY RATINGS*

*Factory wired to VFD.
†Minimum circuit ampacity of 15 amps.

FRAME SIZE

MAX INPUT CURRENT*

MAX OUTPUT CURRENT*

AA

440

442

BA

520

442

BB

520

520

CC

608

608

ITEM

VOLTAGE

MAXIMUM

PROTECTIVE DEVICE

SIZE (AMPS)

WATTS

Controls, Oil Pump And Heater Circuit†

115

15

Oil Pump

115

1.48

130

Oil Sump Heater

115

4.35

500

Oil Vaporizer Heater Circuit†

115

15

Oil Vaporizer Heater

115

13

1500

Electrical data