Microprocessor controls

Microprocessor controls provide the safety, interlock, ca-
pacity control, indications and accessibility necessary to
operate the chiller in a safe and efficient manner.

Control system

The microprocessor control on each Carrier chiller is
factory-mounted, factory-wired, and factory-tested to
ensure machine protection and efficient capacity control.
In addition, the program logic ensures proper starting,
stopping, and recycling of the chiller and provides a com-
munication link to the Carrier Comfort Network® (CCN)
system.

Features

Control system
• Component test and diagnostic check
• Programmable recycle allows chiller to recycle at opti-

mum loads for decreased operating costs

• Menu-driven keypad interface for status display,

set

point control, and system configuration

• CCN system compatible
• Primary and secondary status messages
• Individual start/stop schedules for local and CCN opera-

tion modes

• Recall of up to 25 alarm messages and 25 alert mes-

sages with diagnostic help

• Two chiller lead/lag with third chiller standby is stan-

dard in the PIC III software

• Optional soft stop unloading decreases compressor

speed to unload the motor to the configured amperage
level prior to stopping

• Languages pre-programmed at factory for English, Chi-

nese, Japanese, Korean

• ILT (International Language Translator) available for

conversion of extended ASCII characters

Safety cutouts
• Motor high temperature*†
• Refrigerant (condenser) high pressure*†
• Refrigerant (cooler) low temperature*†
• Lube oil low pressure*
• Compressor (refrigerant) high discharge temperature*
• Under voltage**
• Over voltage**
• Cooler and condenser liquid flow
• Motor overload†
• Motor acceleration time
• Intermittent power loss**
• Motor stall protection
• Low level ground fault
• Cooler and condenser freeze prevention*
• Low oil temperature
• Line voltage imbalance**
• Line current imbalance**
• Line frequency
• Motor current imbalance
• Motor rotation reversal
• Excessive motor amps
• Motor starts limit
• VFD speed out of range
• High VFD rectifier temperature*†

• High VFD inverter temperature*†
• DC bus voltage (Low/High)
Capacity control
• Leaving chilled liquid control
• Entering chilled liquid control
• Soft loading control by temperature or load ramping
• Hot gas bypass valve (optional)
• Power (demand) limiter
• Automatic chilled liquid reset (3 methods)
• Manual speed control
Interlocks
• Manual/automatic remote start
• Starting/stopping sequence

Pre-lube/post-lube
Pre-flow/post-flow

• Compressor run interlock
• Pre-start check of safeties and alerts
• Low chilled liquid (load) recycle
• Monitor/number compressor starts and run hours
• Manual reset of safeties
Indications
• Chiller operating status message
• Power-on
• Pre-start diagnostic check
• Compressor motor amps
• Alert (pre-alarm)††
• Alarm
• Contact for remote alarm
• Safety shutdown messages
• Elapsed time (hours of operation)
• Chiller input kW
• Demand kW
Drive control parameters
• Compressor 100% speed (Hz)
• Rated line voltage
• Rated line amps
• Rated line kW
• Motor rated Load kW
• Motor rated Load amps
• Motor nameplate amps
• Motor nameplate RPM
• Motor nameplate kW
• Inverter PWM frequency

*Can be configured by the user to provide alert indication

at user-defined limit.

†Override protection: Causes compressor to first unload

and then, if necessary, shut down.

**Will not require manual reset or cause an alarm if auto-

restart after power failure is enabled.

††By display code only.

Controls