Appendix p, Technical specification – Amico Nema 4 Master Alarm User Manual
Page 53

www.amico.com
53
Appendix P
Technical Specification
Supply Voltage:
115 to 220 VAC - 50 to 60 Hz
Current Draw:
1 Amp.Max.
Fuse (1/4 * 1-1/4): Fast Blow 1 Amp.
Cable requirement:
Area Display Module to Remote Sensor:
Distance:
Maximum 2,500 feet [750 m]
Cable:
Belden # 8451 or equivalent.
#22 gauge shielded, twisted pair. (For multiple sensors a multi-conductor
twisted pair, shielded cable should be used).
Signal:
30 VDC
-
1.0 Amps.
60 VDC
-
0.3 Amps.
125 VAC
-
0.5 Amps.
Master Module to Source equipment:
Distance:
Maximum 10,000 feet [3,000 m]
Cable:
Minimum #22 gauge wire (does not have to be shielded, twisted pair).
Signal:
5 VDC, < 5 µA.
Computer Interface Board:
Output:
Dry Contacts NC, open on Alarm.
Rating:
30 VDC
-
1.0 Amps.
60 VDC
-
0.3 Amps.
125 VAC
-
0.5 Amps.