Exide Technologies V19CIL5200ULF User Manual
Page 17

Sales
•
Service
•
Recycling 888.563.6300 in the USA 800.268.2698 in Canada
16
APPENDIX A – FAULT CODES
CODE
STATUS
DESCRIPTION
F01
N
Over discharged battery (<1.90vpc after 30 seconds of charge)
F02
N
Deep discharged battery (<1.90vpc after 30 seconds of charge > 1.90vpc)
F03
N Sulphated
battery
F04
S Charger
over
heating
F05
S
Mains failed during charge
F06
R
No output current
F07
C
Incorrect battery < 1.70
F07 (+Y led on)
C
Incorrect battery > 2.25
F09
C
Bulk charge time-out
F10
C
Second stage time-out (Profile Dependant)
F11
C
Incorrect Mains Frequency
F12
C
Control hardware (MCU)
F13
S Thermistor
fault
F16
S
Battery overheating (if temp probe fitted)
F17
C
Auto balance charge time-out
F18
C
Battery disconnected without pausing charge
F19
C
Battery disconnected in cool down period
Key: -
C = critical fault
Ö
charge stopped
Ö
fault code displayed permanently
S = suspend fault
Ö
charge suspended until criteria fulfilled
Ö
fault code displayed permanently
R = retry fault
Ö
charge retries after 20 seconds
Ö
fault code display alternating with standard
display
N = non-critical fault
Ö
charge continues
Ö
fault code display alternating with standard display