Exide Technologies V19CIL5200ULF User Manual
Page 14

Sales
•
Service
•
Recycling 888.563.6300 in the USA 800.268.2698 in Canada
13
11.5 AUTO
BALANCE
The charger maintains a current equal to 32% of the maximum output that is
activated by voltage, on at 2.15VPC and off at 2.35VPC with a time limit of 2 hour if
2.35VPC is not reached.
When current is flowing, amps will be displayed and the yellow LED will be
illuminated. When no current is flowing, the display will show ‘StSt’. The FUNCTION
button can select charge information. The green LED will remain illuminated.
11.6 EQUALIZE
STAGE
Equalize charge consists of 3.5 hours at 32% of the maximum output current with a
voltage limit.
The following table summarizes the action taken when Equalize is set manually
during different charge modes…
Charge Mode
Action
During recharge
Equalize active after termination
After charge termination Equalize active immediately
Smart Start termination
Equalize active after termination
11.7 EQUALIZE
PUSHBUTTON
Equalize charge can be enabled/disabled, when the FUNCTION button is depressed
> 5 second at anytime whilst a battery is connected. Only one equalize charge per
recharge cycle is permitted. The equalize charge can be set in the service mode to
be initiated at ‘x’ number of cycles. X = 0 to 255.
CAUTION:
DO NOT EQUALIZE MORE OFTEN THAN REQUIRED BY THE
CONDITION OF THE BATTERY, AS SPECIFIED IN THE BATTERY
MAINTENANCE INSTRUCTIONS. EXCESSIVE EQUALIZING MAY
DAMAGE THE BATTERY.
11.8 LOW BATTERY OVERRIDE/RECOVORY
11.8.1 CONFIGURATION
There is the ability to manually override the low ‘Incorrect Battery’ threshold of
1.70 VPC, down to a minimum of 1.00 VPC - the level at which the charger will
recognize a battery connection. This is achieved by holding the FUNCTION
push button for 5 seconds when the incorrect battery fault has been detected.
11.8.2 OPERATION
If ‘Low Battery Override’ has been enabled and a battery (voltage > 1.00 VPC)
is connected to the charger, the charger will pass current at 75% of maximum
current output the charger rated output current level.