Exide Technologies V19CIL5200ULF User Manual
Page 10

Sales
•
Service
•
Recycling 888.563.6300 in the USA 800.268.2698 in Canada
9
6.2
AC VOLTAGE CONNECTIONS
To connect the input AC voltage, route the AC conduit through the knockout hole
provided. Continue the AC wiring to the breaker terminals L1 (N) and L2 (L) (single
phase input) or L1, L2, and L3 (three phase input). For proper connection, torque the
screws to approximately 25 inch-pounds.
6.3 GROUND
CONNECTION
It is a requirement to ground the chassis while the charger is connected to AC power.
The charger comes with a threaded M6 hole, clearly marked on the chassis. To
ensure good continuity, keep the contact area clean.
WARNING: DO NOT OPERATE THE UNIT WITHOUT PROPER GROUNDING.
IMPROPER GROUNDING CAN RESULT IN THE RISK OF AN ELECTRIC
SHOCK.
CAUTION: USE MINIMUM 75°C WIRING FOR SUPPLY CONNECTIONS. GROUND
THE CHARGER PROPERLY USING THE THREADED M6 HOLE (GND)
PROVIDED. USE COPPER-CLAD ALUMINUM, ALUMINUM OR
COPPER CONDUCTORS ONLY.
After electrical connection is completed, the charger is ready for operation.