During the 10-minute Refresh Charge period the display will toggle between ‘rEFr ’
and the output current. The yellow LED is illuminated and the green LED will remain
illuminated and the FUNCTION button can select charge status.
The charger will remain in the Refresh Charge stage until the battery is
disconnected.
11.12 CHARGE TIME
The amount of time a battery charges will vary depending on the depth of discharge
(DOD). Once the battery has reached 80% charged, the cycle will be terminated after
3.5 hours or less if terminated by dV/dt. Normal charge cycles will average about 8
hours total.
11.13 INCORRECT BATTERY LIMITS
Incorrect battery detection limits will be < 1.70 VPC and > 2.25 VPC (off charge). If
the battery voltage comes within this window the charger will automatically
commence charging.
11.14 CHARGE CYCLE RESET
A charge cycle is reset when a battery is disconnected and a battery is reconnected.
11.15 AC POWER FAILURE
If the AC power fails during a charge cycle, the charger will resume the cycle at the
point of termination as soon as AC power is restored.
12. MAINTENANCE
The charger requires minimum maintenance. ENSURE THE CHASSIS IS SECURELY
GROUNDED per the local/federal Electrical Code. Do not allow excessive dust to
accumulate on the components inside. Blow out with clean compressed air when
necessary. The chargers are designed with a breaker and fuse for the AC input and DC
output respectively. Should this fuse fail or breaker trip, the cause must be determined
before they are corrected or replaced. Never replace the fuse or breaker with one of a
higher capacity than the one originally fitted.