14

If less than 3.0VPC, current will flow for 5 minutes and the charge will be
suspended for 5 minutes. The cycle is repeated until the battery voltage is
greater than 1.70 VPC at the end of the 5-minute rest period.

If the battery voltage is greater than 1.70 VPC at the end of the 5-minute rest
period, the battery recovery mode will cease and charge will start from stage 1
with smart start disabled.

If 3.0 VPC is reached within the 5 minutes of charge, the charge will be
suspended equal to the ‘on’ time, maximum of 5 minutes. During this period
the display will show ‘Lobt’. During the 5-minute off period the display will
show the battery volts per cell alternating with ‘Lobt’.

11.9 DELAYED START OF CHARGE

A charge delay can be set in the service mode. The time is 0 to 48 hours in 1-hour
steps; this is permanently set for every charge cycle.

The display will show ‘dELy’ and alternate with the time remaining before charge
starts.

11.10 BATTERY COOLDOWN OPERATION STAGE

The cool down period begins after charge termination and is equal to the time spent
on charge.

During the cool down period, the green LED will flash and the display will show
‘CooL’ alternating with the remaining cool down time. The FUNCTION button can
select charge information and display this momentarily.

Once the cool down period is complete, the charger will illuminate the green LED
and enter the refresh stage.

If the battery is disconnected before completion of the cool down period, the
countdown will cease and the display will show F19.

If equalize is activated during cool down, the cool down timer will be suspended until
Equalize is complete, whereupon the cool down timer countdown will resume.

11.11 REFRESH CHARGE STAGE

The Refresh Charge activates every 24 hours after the standard charge cycle, if the
battery remains connected to the charger. The Refresh Charge stage lasts for 10
minutes and consists of Finish Rate or 32% of the maximum output current.

The 24-hour refresh delay starts after termination of recharge or Equalize. During
the refresh off period the display will show ‘rEdy’. The green LED will remain
illuminated. The FUNCTION button can select charge information.