Appendix 1: input wiring requirements – Tweco FP-55 User Manual
Page 35

Manual 0-2846
A-1
APPENDIX
APPENDIX 1: INPUT WIRING REQUIREMENTS
NOTES
The table above is based on the following output current and voltage: 125 vdc @ 40A
Refer to Local and National Codes or local authority having jurisdiction for proper wiring requirements.
Cable size is de-rated based on the Duty Cycle of the equipment.
The suggested sizes are based on flexible power cable with power plug installations. For hard-wired installations refer
to local or national codes.
Cable conductor temperature used is 167° F (75° C).
An energy limiting fuse UL Class RK-1 (examples: BUSS LPS/LPN-RK or Gould-Shawmut AZK-A6K) should be
used to minimize damage to Plasma Cutting, Welding or power distribution equipment.
NEVER
use replaceable element fuses like UL Class H, or "one-time" fuses like UL Class K5.
Power Input Current Input
Voltage
Frequency
1-Ph
1-Ph
Fuse (Amps)
Wire (AWG) Wire (Canada)
(Volts)
(Hz)
(kVA)
(Amps)
1-Ph
1-Ph
1-Ph
208
60
8.2
39
45
8
8
230
60
8.2
37
45
8
8
Suggested Sizes (See Notes)
Input
Line Voltages with Suggested Circuit Protection and Wire Sizes
Based on National Electric Code and Canadian Electric Code