beautypg.com

Pounds of salt per minute of fill. step 2ss, Step 3ss – Watts W100F User Manual

Page 14

background image

Page 1

WS1TC & WS1.25 TC Manual

OEM General Instructions

The control valve offers multiple procedures that allow the valve to be modified to suit the needs of the installation. These
procedures are:

• OEM System Setup

• Installer Displays & Settings (either 1-99 Days Between Regeneration option or 7-Day option)

• User Displays

These procedures can be accessed in any order. Details on each of the procedures are provided below and on the following pages.

When in operation, normal user displays show the time of day or days remaining before regeneration. When stepping through a
procedure, if no buttons are pressed within five minutes the display returns to a normal user display. Any changes made prior to the
five minute time out are incorporated.

To quickly exit Installer Displays & Settings or OEM Setup, simultaneously press SET HOUR + DOWN. Any changes made prior
to the exit are incorporated.

To reinitialize the control valve, check to make sure the valve is in the User Display. Then simultaneously press SET HOUR +
DOWN or unplug power source plug (black wire) on the circuit board, and plug back in.

STEP 1SS

OEM System Setup

STEP 1SS – From normal mode, press SET HOUR + UP buttons simultaneously for 3 seconds
and release. Then press SET HOUR + UP buttons simultaneously for 3 seconds and release.

STEP 2SS – Choose the desired program by pressing the UP or DOWN buttons. Prior to

selecting a program, verify the correct valve body, main piston, regenerant piston, and stack are
being used, and that the injector or injector plug(s) are in the correct locations. See Compliance
Table in Service Instructions under Injector Cap, Screen, Injector Plug and Injector section and

Figure 6. Press SET HOUR button to go to Step 3SS.

STEP 3SS – If program P0 through P6 was selected, enter in the minutes of fill using the UP or
DOWN buttons. The allowable values vary from a low of 1 to a high of 99. If program P7, P8
or P9 was selected, dashes will appear for minutes of fill. Press SET HOUR button to go to Step
4SS. Note: For each minute of fill 0.5 gallons of water is added to the solution tank. With salt
(sodium chloride) this equates to approximately 1

1

/

2

pounds of salt per minute of fill.

STEP 2SS

STEP 3SS

Regeneration Cycles and Times for Different Programs

Program

All times in Minutes

C1

1st Backwash

C2

Regenerate

C3

2nd Backwash

C4

Rinse

C5

Fill

P0

3

50

3

3

1-99

P1

8

50

8

4

1-99

P2

8

70

10

6

1-99

P3

12

70

12

8

1-99

P4

10

50

Skipped

8

1-99

P5

4

50

Skipped

4

1-99

P6

12

6

Skipped

12

1-99

P7

6

Skipped

Skipped

4

Skipped

P8

10

Skipped

Skipped

6

Skipped

P9

14

Skipped

Skipped

8

Skipped