beautypg.com

Installation, Location selection, Water line connection – Watts Autotrol 263 / 268 (400 Series) User Manual

Page 3: Drain line connection

background image

3

Installation

All plumbing and electrical connections must conform
to local codes.

Inspect unit carefully for carrier shortage or shipping
damage.

Location Selection

1. The distance between the unit and a drain should be

as short as possible.

2. If it is likely that supplementary water treatment

equipment will be required, make certain adequate
additional space is available.

3. Since salt must be added periodically to the brine

tank, the location should be easily accessible.

4. Do not install any unit closer to a water heater than

a total run of 10 feet (3 m) of piping between the
outlet of the conditioner and the inlet to the heater.
Water heaters can sometimes overheat to the
extent they will transmit heat back down the cold
pipe into the unit control valve.

Hot water can severely damage the conditioner. A
10-foot (3-m) total pipe run, including bends,
elbows, etc., is a reasonable distance to help
prevent this possibility. A positive way to prevent
hot water flowing from heat source to the
conditioner, in the event of a negative pressure
situation, is to install a check valve in the soft
water piping from the conditioner. If a check valve
is installed, make certain the water heating unit
is equipped with a properly rated temperature
and pressure safety relief valve. Also, be
certain that local codes are not violated.

5. Do not locate unit where it or its connections

(including the drain and overflow lines) will ever be
subjected to room temperatures under 34

o

F (1

o

C)

or over 120

o

F (49

o

C).

6. Do not install unit near acid or acid fumes.

7. The use of resin cleaners in an unvented enclosure

is not recommended.

Water Line Connection

The installation of a bypass valve system is
recommended to provide for occasions when the water
conditioner must be bypassed for hard water or for
servicing.

The most common bypass systems are the Autotrol
Series 1265 bypass valve (Figure 1) and plumbed-in
globe valves (Figure 2). Though both are similar in
function, the Autotrol Series 1265 bypass offers
simplicity and ease of operation.

Figure 1 - Autotrol Series 1265 Bypass Valve

Figure 2 - Typical Globe Valve Bypass System

Drain Line Connection

Note:

Standard commercial practices are expressed

here. Local codes may require changes to the following
suggestions.

1. Ideally located, the unit will be above and not more

than 20 feet (6.1 m) from the drain. For such
installations, using an appropriate adapter fitting,
connect 1/2-inch (1.3-cm) plastic tubing to the drain
line connection of the control valve.

2. If the backwash flow rate exceeds 5 gpm

(22.7 Lpm) or if the unit is located more than 20 feet
(6.1 m) from drain, use 3/4-inch (1.9-cm) tubing for
runs up to 40 feet (12.2 m). Also, purchase
appropriate fitting to connect the 3/4-inch tubing to
the 3/4-inch NPT drain connection.

3. If the unit is located where the drain line must be

elevated, you may elevate the line up to 6 feet
(1.8 m) providing the run does not exceed
15 feet (4.6 m) and water pressure at conditioner is
not less than 40 psi (2.76 bar). You may elevate an
additional 2 feet (61 cm) for each additional
10 psi (0.69 bar).

Not in Bypass

In Bypass

BY

PA

SS

BY

PA

SS

B

Y

P

A

S

S

B

Y

P

A

S

S

Water

Conditioner

In

Out

Water

Conditioner

In

Out

Water

Water

Not in Bypass

In Bypass

Water

Conditioner

Water

Conditioner